STAND ALONE UPS SYSTEMS

MODULAR UPS SYSTEMS

BATTERIES & RECTIFIERS


SOLAR PRODUCTS


C & D 12V LBTY

 

Front Access

 

Valve Regulated Lead Acid Battery

Applications


  • Telecommunications
  • DC Systems
  • Customer Promises
  • Broadband
  • PBX
  • Microwave Repeater
  • Fiber Optic Regen Sites
  • Fixed Wireless

Features


  • Design life (25°C): 10 years
  • Flame-arresting one-way pressurerelief
    vent for safety and long life.
  • Absorbent Glass Mat (AGM)
    technology for efficient gas
    recombination of up to 99% and
    freedom from electrolyte maintenance.
  • Computer designed lead, low Calcium
    alloy grid for minimal gassing and ease
    of recycling.
  • Front terminal design, convenient for
    battery maintenance, increasing safety,
    and saving the installation room

 


  • UL-recognized component.
  • Can be used in any orientation.
    Upright, side, or end mounting
    recommended.
  • Not restricted for air transport –
    Complies with IATA/ICAO Special
    Provision A67.
  • Not restricted for surface transport –
    classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189
  • Not restricted for water transport –
    classified as non-hazardous material
    per IMDG Amendment 27

Specifications


Model V Capacity/AH
(C10,1.75V@25°C)
Dimensions (L*W*H*total height mm) Weight
(Kg)
Resistance
mΩ
Container
Materials
C&D 12F-55 LBT 12 55 227 106 222 222 18 6 ABS
C&D 12F-90 LBT 12 90 563 114 188 188 26.5 5.8 ABS
C&D 12F-105 LBT 12 105 508 111 236 236 32.5 5 ABS
C&D 12F-125 LBT 12 125 436 107 317 323 41.5 5 ABS
C&D 12F-135 LBT 12 135 551 109 239 239 41 3.8 ABS
C&D 12F-150 LBT 12 150 555 110 288 288 45 4 ABS
C&D 12F-180 LBT 12 180 546 125 317 325 53.5 4 ABS
Operating Temperature Range Discharge: -20°C to 60°C; Charge: 0°C to 50°C; Storage: -20°C to 60°C
Recommended Operating Temperature Range 25°C ± 5°C
Floating Charging Voltage 13.6 to 13.8 VDC/unit Average at 25°C
Recommended Maximum Charging Current Limit 0.3C10 A @ 10 hr. rate
Equalization and Cycle Service Charging Voltage 14.6 to 14.8 VDC/unit Average at 25°C
Maximum Discharging Current Limit 10C10 A @ 10 hr. rate
Self Discharge BATTERIES & RECTIFIERS may be stored for up to 6 months at 25°C, and self-discharge rate less
than 3% per month. Please charging the battery before using.
Accessories Inter unit connectors, racks and cabinet systems are available

Battery Dimesions Schematics


C&D 12F-55 LBT
C&D 12F-90 LBT
C&D 12F-105 LBT
C&D 12F-125 LBT
C&D 12F-135 LBT
C&D 12F-150 LBT
C&D 12F-180 LBT

C & D 12F-55 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 221.67 172.53 139.53 96.40 61.60 35.18 25.25 20.90 17.22 12.21 10.10 5.27
1.80 256.83 194.33 156.27 102.88 65.02 36.88 26.57 21.95 18.13 12.66 10.44 5.50
1.75 285.50 214.00 170.07 107.80 66.67 37.43 27.23 22.55 18.42 12.94 10.55 5.55
1.70 317.17 231.50 178.37 110.30 67.32 37.78 27.38 22.72 18.58 13.05 10.66 5.61
1.67 327.00 239.50 180.82 111.60 67.82 38.13 27.55 22.83 18.65 13.16 10.72 5.66
1.60 336.00 250.83 184.67 113.02 68.15 38.28 27.62 22.88 18.77 13.21 10.83 5.72

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 127.8 97.68 78.14 53.85 32.4 18.32 13.15 10.84 8.923 6.277 5.388 2.666
1.80 146.8 109.3 87.12 57.48 34.1 19.17 13.75 11.39 9.324 6.554 5.554 2.833
1.75 162.6 119.9 94.51 60.12 34.93 19.52 14.14 11.66 9.495 6.665 5.61 2.888
1.70 181.1 129.9 99.26 61.66 35.26 19.67 14.19 11.77 9.61 6.721 5.666 2.944

C&D 12F-90 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 362.83 282.33 228.33 157.75 100.80 57.58 41.32 34.20 28.17 19.98 16.53 8.63
1.80 420.33 317.83 255.67 168.33 106.38 60.37 43.47 35.92 29.67 20.72 17.08 8.99
1.75 467.33 350.17 278.33 176.33 109.08 61.27 44.55 36.90 30.13 21.17 17.27 9.09
1.70 519.00 378.83 291.83 180.50 110.17 61.83 44.82 37.17 30.42 21.35 17.45 9.18
1.67 535.00 392.00 295.83 182.67 110.97 62.40 45.08 37.35 30.52 21.53 17.53 9.27
1.60 549.67 410.33 302.17 185.00 111.52 62.65 45.18 37.43 30.70 21.62 17.72 9.36

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 209.1 159.8 127.9 88.11 53.01 29.98 21.51 17.73 14.6 10.27 8.816 4.363
1.80 240.2 178.8 142.6 94.05 55.8 31.37 22.5 18.63 15.26 10.73 9.089 4.635
1.75 266.1 196.1 154.7 98.37 57.15 31.94 23.13 19.08 15.54 10.91 9.18 4.726
1.70 296.4 212.5 162.4 100.9 57.69 32.19 23.22 19.26 15.72 11 9.271 4.817

C&D 12F-105 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 423.33 329.33 266.33 184.00 117.60 67.17 48.20 39.90 32.87 23.32 19.28 10.07
1.80 490.33 370.83 298.33 196.33 124.12 70.42 50.72 41.90 34.62 24.17 19.93 10.49
1.75 545.17 408.50 324.67 205.83 127.27 71.47 51.98 43.05 35.17 24.70 20.13 10.60
1.70 605.50 442.00 340.50 210.50 128.52 72.13 52.28 43.37 35.48 24.90 20.35 10.71
1.67 624.17 457.33 345.17 213.00 129.47 72.82 52.60 43.58 35.60 25.12 20.45 10.81
1.60 641.33 478.83 352.50 215.83 130.10 73.10 52.72 43.68 35.82 25.22 20.67 10.92

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 243.9 186.5 149.2 102.8 61.85 34.97 25.1 20.69 17.04 11.98 10.29 5.09
1.80 280.2 208.7 166.3 109.7 65.1 36.6 26.25 21.74 17.8 12.51 10.6 5.408
1.75 310.5 228.8 180.4 114.8 66.68 37.26 26.99 22.26 18.13 12.72 10.71 5.514
1.70 345.7 248 189.5 117.7 67.31 37.55 27.09 22.47 18.35 12.83 10.82 5.62

C&D 12F-125 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 504.00 392.17 317.17 219.17 140.00 79.97 57.38 47.50 39.13 27.77 22.97 11.99
1.80 583.83 441.50 355.17 233.83 147.75 83.83 60.38 49.88 41.22 28.77 23.72 12.49
1.75 649.00 486.33 386.50 245.00 151.50 85.08 61.88 51.25 41.87 29.40 23.97 12.62
1.70 720.83 526.33 405.33 250.67 153.00 85.88 62.25 51.63 42.25 29.65 24.23 12.74
1.67 743.17 544.33 411.00 253.67 154.13 86.68 62.63 51.88 42.38 29.90 24.35 12.87
1.60 763.50 570.00 419.67 256.83 154.88 87.02 62.75 52.00 42.63 30.03 24.60 13.00

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 290.4 222 177.6 122.4 73.63 41.63 29.88 24.63 20.28 14.26 12.25 6.06
1.80 333.6 248.4 198 130.6 77.5 43.57 31.25 25.88 21.19 14.9 12.62 6.44
1.75 369.6 272.4 214.8 136.6 79.38 44.36 32.13 26.5 21.58 15.15 12.75 6.56
1.70 411.6 295.2 225.6 140.1 80.13 44.7 32.25 26.75 21.84 15.27 12.88 6.69

C&D 12F-135 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 544.33 423.50 342.50 236.67 151.20 86.37 61.97 51.30 42.27 29.98 24.80 12.95
1.80 630.50 476.83 383.50 252.50 159.57 90.53 65.20 53.87 44.50 31.07 25.62 13.49
1.75 701.00 525.17 417.50 264.50 163.62 91.90 66.83 55.35 45.22 31.75 25.88 13.63
1.70 778.33 568.33 437.83 437.83 165.23 92.75 67.23 55.75 45.63 32.02 26.17 13.76
1.67 802.50 588.00 443.83 443.83 166.45 93.62 67.63 56.03 45.77 32.30 26.30 13.90
1.60 824.67 615.50 453.17 453.17 167.33 93.98 67.66 56.17 46.05 32.43 26.57 14.04

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 131.6 239.8 191.8 132.2 79.52 44.96 32.27 26.6 21.9 15.41 13.22 6.54
1.80 360.3 268.3 213.8 141.1 83.7 47.05 33.75 27.95 22.89 16.09 13.63 6.95
1.75 399.2 294.2 232 147.6 85.73 47.91 34.7 28.62 23.31 16.36 13.77 7.09
1.70 444.5 318.8 243.6 151.3 86.54 48.28 34.83 28.89 23.59 15.5 13.91 7.23

C&D 12F-150 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 604.67 470.50 380.50 262.83 168.00 95.97 68.85 57.00 46.95 33.32 27.55 14.38
1.80 700.50 529.83 426.17 280.50 177.33 100.60 72.45 59.85 49.45 34.52 28.47 14.99
1.75 778.83 583.50 463.83 294.00 181.83 102.10 74.25 61.50 50.23 35.28 28.77 15.14
1.70 864.83 631.50 486.50 300.833 183.67 103.05 74.70 61.95 50.70 35.58 29.07 15.29
1.67 891.67 563.33 493.17 304.33 185.00 104.02 75.15 62.25 50.85 35.88 29.22 15.44
1.60 916.17 684.00 503.67 308.17 185.83 104.42 75.30 62.40 51.17 36.03 29.52 15.60

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 348.5 266.4 213.1 146.9 88.35 49.96 35.85 29.55 24.34 17.12 14.69 7.271
1.80 400.3 298.1 237.6 156.8 93 52.28 37.5 31.05 25.43 17.88 15.15 7.726
1.75 443.5 326.9 257.8 164 95.25 53.24 38.55 31.8 25.9 18.18 15.3 7.877
1.70 493.9 354.2 270.7 168.2 96.15 53.64 38.7 32.1 26.21 18.33 15.45 8.029

C&D 12F-180 LBT

Constant Power Discharge Table - Watts Per Cell @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 725.67 564.67 456.67 315.50 201.67 115.15 82.62 68.40 56.35 39.97 33.07 17.27
1.80 840.677 635.83 511.33 336.67 212.83 120.72 86.93 71.82 59.35 41.43 34.15 17.98
1.75 934.67 100.17 556.67 352.83 218.17 122.52 89.10 73.80 60.28 42.33 34.52 10.17
1.70 1037.83 757.83 583.67 361.00 220.33 123.67 89.63 74.33 60.8 42.70 34.88 18.35
1.67 1099.50 820.83 604.33 369.83 223.00 125.30 90.37 74.88 61.40 43.25 35.43 18.72
1.60 1070.00 784.00 591.86 365.33 222.00 124.82 90.10 74.70 61.03 43.07 35.07 18.53

Constant Current Discharge Table - Amps @ 25°C (77°F)


End Voltage Per Cell 5min 10min 15min 30min 1hr 2hr 3hr 4hr 5hr 8hr 10hr 20hr
1.85 418.2 319.7 255.7 176.2 106 59.95 43.02 35.46 29.2 20.54 17.63 8.726
1.80 480.4 357.7 285.1 188.1 111.6 62.74 45 37.26 30.51 21.45 18.18 9.271
1.75 532.2 392.3 309.9 196.7 114.3 63.88 46.26 46.26 31.08 21.81 18.36 9.453
1.70 592.7 425.1 324.9 201.8 115.4 64.37 46.44 46.44 31.45 22 18.54 9.634