STAND ALONE UPS SYSTEMS

MODULAR UPS SYSTEMS

BATTERIES & RECTIFIERS


SOLAR PRODUCTS


12-1054 - MRX

 

UPS12-100MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-100 MRXF 176 133 106 87.1 66.3 55.4 49.9 46.9 40.8 29.4 34 AH 30 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 10.7 171 1003 12.35

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware
Initial Torque
30 in.-lbs. (3.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 156 119 93.5 78.0 60.5 51.1 46.3 43.7 38.4 27.9
1.70 162 123 97 80.6 61.9 52.1 47.1 44.4 38.9 28.2
1.67 166 125 99 82.1 62.8 52.7 47.6 44.8 39.1 28.3
1.65 168 128 101 83.1 63.3 53.0 47.9 45.0 39.4 28.5

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 166 126 99.5 82.8 63.9 53.7 48.6 45.7 40.0 29.0
1.70 172 131 103 85.5 65.4 54.7 49.4 46.4 40.5 29.3
1.67 176 133 106 87.1 66.3 55.4 49.9 46.9 40.8 29.4
1.65 179 136 107 88.2 66.9 55.8 50.2 47.1 41.0 29.6

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 19.3 11.0 7.88 5.21 3.48 2.88 2.45 1.57 1.33
1.80 20.2 11.4 8.19 5.41 3.60 2.98 2.54 1.63 1.39
1.75 20.6 11.6 8.34 5.46 3.67 3.03 2.58 1.64 1.39

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 20.1 11.4 8.17 5.39 3.59 2.95 2.51 1.61 1.37
1.80 21.0 11.9 8.49 5.59 3.71 3.06 2.61 1.67 1.42
1.75 21.5 12.1 8.64 5.65 3.78 3.10 2.64 1.68 1.43

 

 

back to top

 

 

UPS12-130MRX

 

UPS12-130MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-130 MRXF 225 176 135 109 80.7 66.4 59.3 55.4 47.6 34.1 35 AH 31 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 11.5 216 1321 9.38

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware
Initial Torque
30 in.-lbs. (3.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 201 156 122 99.0 74.0 61.4 55.0 51.6 44.6 32.2
1.70 208 162 126 102 75.5 62.6 56.1 52.5 45.4 32.6
1.67 212 165 127 103 76.4 63.2 56.5 52.9 45.7 32.8
1.65 214 168 129 104 77.0 63.7 56.9 53.3 46.0 33.0

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 214 166 130 105 78.2 64.5 57.7 54.0 46.5 33.5
1.70 221 172 134 108 79.8 65.8 58.8 55.0 47.3 33.9
1.67 225 176 135 109 80.7 66.4 59.3 55.4 47.6 34.1
1.65 228 179 137 110 81.4 66.9 59.7 55.8 47.9 34.3

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 22.9 12.4 8.68 5.53 3.65 3.01 2.56 1.63 1.39
1.80 24.1 13.0 9.09 5.78 3.81 3.14 2.67 1.69 1.44
1.75 24.5 13.2 9.28 5.88 3.87 3.19 2.71 1.71 1.45

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 23.8 12.9 9.00 5.72 3.77 3.09 2.63 1.67 1.42
1.80 25.1 13.5 9.42 5.97 3.93 3.22 2.74 1.74 1.47
1.75 25.5 13.7 9.62 6.09 3.99 3.27 2.78 1.76 1.49

 

 

back to top

 

 

UPS12-150MRX

 

UPS12-150MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-150 MRXF 249 189 150 119 86.5 70.0 61.8 57.4 48.7 34.3 36 AH 32 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 12.4 269 1475 8.45

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware
Initial Torque
30 in.-lbs. (3.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 222 169 134 108 79.5 65.1 57.8 53.9 46.2 32.6
1.70 231 174 138 111 81.4 66.3 58.6 54.6 46.6 32.9
1.67 234 178 141 113 81.9 66.6 58.9 54.9 46.8 33.0
1.65 236 181 143 114 82.4 67.0 59.2 55.1 46.9 33.2

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 236 180 143 115 84.0 68.4 60.6 56.4 48.1 33.9
1.70 246 185 147 118 56.0 69.7 61.5 57.2 48.5 34.2
1.67 249 189 150 119 86.5 70.0 61.8 57.4 48.7 34.3
1.65 251 192 152 121 87.0 70.4 62.1 57.7 48.9 34.5

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 24.2 13.0 9.08 5.75 3.78 3.11 2.64 1.67 1.42
1.80 25.3 13.6 9.47 5.97 3.92 3.22 2.73 1.72 1.46
1.75 25.7 13.8 9.56 6.04 3.97 3.27 2.78 1.76 1.49

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 25.2 13.5 9.41 5.94 3.90 3.19 2.71 1.71 1.45
1.80 26.4 14.2 9.81 6.18 4.04 3.30 2.80 1.76 1.49
1.75 26.8 14.3 9.91 6.24 4.10 3.35 2.85 1.80 1.53

 

 

back to top

 

UPS12-200MRX

 

UPS12-200MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-200 MRXF 342 257 202 162 122 100 89.0 83.2 71.7 50.9 55 AH 48 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 17.7 320 1472 8.58

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware
Initial Torque
30 in.-lbs. (3.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 304 228 182 149 112 93.1 83.5 78.4 68.0 48.7
1.70 313 234 186 152 114 94.3 84.5 79.2 68.4 48.7
1.67 318 238 188 153 115 94.8 84.8 79.5 68.6 48.9
1.65 322 241 190 154 115 95.4 85.2 79.8 68.8 49.1

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 323 242 194 158 118 97.9 87.6 82.0 70.8 50.7
1.70 333 249 198 161 120 99.1 88.6 82.8 71.3 50.7
1.67 339 254 200 162 121 100 89.0 83.2 71.5 50.9
1.65 342 257 202 164 122 100 89.4 83.5 71.7 51.1

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 34.3 18.8 13.2 8.49 6.65 4.68 3.99 2.56 2.18
1.80 36.0 19.7 13.8 8.87 5.89 4.87 4.15 2.66 2.26
1.75 36.4 20.1 14.1 9.03 6.00 4.96 4.22 2.70 2.30

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 35.7 19.5 13.7 8.78 5.83 4.80 4.09 2.62 2.24
1.80 37.5 20.5 14.3 9.17 6.08 5.00 4.26 2.72 2.32
1.75 37.9 20.9 14.6 9.34 6.18 5.08 4.33 2.77 2.36

 

 

back to top

 

 

UPS12-220MRX

 

UPS12-220MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-220 MRXF 372 278 220 178 132 110 98.5 92.3 79.8 57.7 56 AH 49 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 19 383 1985 6.37

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware
Initial Torque
30 in.-lbs. (3.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 334 251 198 163 123 103 92.4 86.8 75.5 54.9
1.70 345 257 204 166 124 104 93.3 87.7 76.2 55.3
1.67 349 261 207 168 125 104 93.9 88.2 76.6 55.5
1.65 352 263 209 169 126 105 94.2 88.4 76.8 55.7

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 355 267 211 172.5 130 108 96.9 90.8 78.7 57.1
1.70 367 274 217 176.3 131 109 97.9 91.7 79.4 57.5
1.67 372 278 220 178.2 132 110 98.5 92.3 79.8 57.7
1.65 375 280 222 179.5 133 110 98.8 92.5 80.0 57.9

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 37.1 20.0 14.0 8.83 5.80 4.76 4.04 2.55 2.16
1.80 38.2 20.6 14.4 9.15 6.03 4.97 4.22 2.68 2.28
1.75 39.1 21.1 14.7 9.32 6.14 5.05 4.29 2.72 2.31

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 38.6 20.8 14.5 9.13 5.97 4.88 4.14 2.61 2.22
1.80 39.8 21.4 14.9 9.46 6.22 5.10 4.33 2.75 2.34
1.75 40.7 21.9 15.2 9.64 6.33 5.18 4.40 2.79 2.37

 

 

back to top

 

 

UPS12-280MRX

 

UPS12-280MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77&deg,F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-280 MRXF 482 351 284 234 178 149 134 126 109 79.7 83 AH 73 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 25.7 475 2099 5.99

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt..
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 426 314 256 212 163 137 124 117 103 75.5
1.70 445 324 262 217 166 140 126 119 104 76.2
1.67 453 330 267 220 169 141 128 120 105 76.6
1.65 465 337 271 223 170 143 129 121 106 77.2

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 453 334 272 225 172 144 130 123 107 78.5
1.70 473 345 279 230 175 147 132 124 109 79.3
1.67 482 351 284 234 178 149 134 126 109 79.7
1.65 495 358 288 237 180 150 135 127 110 80.3

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 52.2 28.5 20.0 12.8 8.49 7.01 5.98 3.82 3.25
1.80 54.7 29.9 21.0 13.4 8.89 7.34 6.25 3.98 3.39
1.75 55.5 30.5 21.4 13.7 9.04 7.46 6.35 4.05 3.44

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 54.3 29.6 20.7 13.2 8.75 7.19 6.13 3.91 3.33
1.80 57.0 31.1 21.8 13.9 9.16 7.53 6.41 4.09 3.48
1.75 57.8 31.7 22.2 14.1 9.32 7.65 6.51 4.15 3.53

 

 

back to top

 

 

UPS12-320MRX

 

UPS12-320MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-320 MRXF 544 413 326 267 200 165 148 138 119 86.2 84 AH 77 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 27.1 500 2381 5.29

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 495 371 295 242 184 154 139 130 114 82.2
1.70 503 382 302 248 188 156 140 131 114 82.6
1.67 512 388 307 251 190 157 141 132 114 82.9
1.65 515 393 310 254 192 159 142 133 115 83.1

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 526 395 314 257 194 162 145 136 118 85.5
1.70 535 406 321 263 199 164 147 138 119 85.9
1.67 544 413 326 267 200 165 148 138 119 86.2
1.65 547 418 329 269 203 167 149 139 119 86.5

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 55.7 30.6 21.6 14.0 9.12 7.45 6.29 3.91 3.30
1.80 58.2 31.9 22.4 14.6 9.46 7.72 6.51 4.04 3.41
1.75 59.5 32.5 22.8 14.9 9.61 7.83 6.60 4.09 3.45

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 58.00 31.80 22.37 14.48 9.40 7.64 6.45 4.01 3.39
1.80 60.67 33.14 23.26 15.06 9.76 7.92 6.68 4.14 3.49
1.75 62.01 33.76 23.66 15.39 9.90 8.03 6.77 4.20 3.54

 

 

back to top

 

 

UPS12-370MRX

 

UPS12-370MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-370 MRXF 634 485 376 309 234 195 176 165 144 100 102 AH 90 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 31.5 541 2734 4.65

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 602 454 363 305 239 201 182 172 151 107
1.70 624 473 376 314 244 205 185 174 152 108
1.67 634 486 383 319 247 207 186 175 153 108
1.65 639 491 387 322 250 208 188 176 153 109

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 605 461 359 297 227 190 171 161 140 98.8
1.70 623 475 370 305 231 193 174 164 143 100
1.67 633 485 376 309 234 195 176 165 144 100
1.65 641 491 381 312 236 197 177 167 145 101

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 71.9 38.9 27.2 17.3 11.4 9.41 8.00 5.08 4.32
1.80 75.5 40.7 28.4 18.0 11.9 9.76 8.29 5.25 4.46
1.75 76.5 41.3 28.8 18.4 12.1 9.93 8.43 5.33 4.52

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 67.4 36.7 25.7 16.4 10.9 8.92 7.60 4.86 4.14
1.80 69.3 37.8 26.5 17.0 11.3 9.26 7.90 5.05 4.31
1.75 71.0 38.6 27.1 17.3 11.4 9.41 8.02 5.12 4.36

 

 

back to top

 

 

UPS12-400MRX

 

UPS12-400MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-400 MRXF 674 517 408 339 261 218 196 183 159 113 109 AH 97 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 35.3 572 3059 4.06

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt..
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 602 454 363 305 239 201 182 172 151 107
1.70 624 473 376 314 244 205 185 174 152 108
1.67 634 486 383 319 247 207 186 175 153 108
1.65 639 491 387 322 250 208 188 176 153 109

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 640 483 386 324 252 212 191 180 157 111
1.70 664 503 400 333 258 215 194 182 158 112
1.67 674 517 408 339 261 218 196 183 159 113
1.65 679 522 412 342 264 219 197 184 160 113

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 71.9 38.9 27.2 17.3 11.4 9.41 8.00 5.08 4.32
1.80 75.5 40.7 28.4 18.0 11.9 9.76 8.29 5.25 4.46
1.75 76.5 41.3 28.8 18.4 12.1 9.93 8.43 5.33 4.52

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 74.8 40.4 28.2 17.9 11.8 9.7 8.21 5.21 4.43
1.80 78.7 42.3 29.4 18.6 12.2 10.0 8.51 5.39 4.57
1.75 79.7 42.9 29.8 19.0 12.5 10.2 8.65 5.46 4.64

 

 

back to top

 

 

UPS12-550MRX

 

UPS12-550MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-550 MRXF 897 704 550 454 346 288 258 242 210 148 154 AH 137 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 48.6Kg 821 3609 3.48

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 747 597 478 398 307 261 237 224 198 140
1.70 804 635 502 414 316 266 242 228 200 141
1.67 843 662 517 428 328 273 246 231 201 142
1.65 872 672 527 435 332 276 248 232 202 143

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 795 636 509 422 324 274 249 235 206 146
1.70 855 675 534 439 334 280 253 238 208 147
1.67 897 704 550 454 346 288 258 242 210 148
1.65 928 715 561 462 350 290 260 243 210 149

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 93.4 54.9 38.3 24.4 16.1 13.3 11.3 7.15 6.08
1.80 99.1 57.7 40.2 25.5 16.8 13.8 11.7 7.41 6.29
1.75 102 59.1 41.1 26.0 17.0 14.0 11.9 7.50 6.36

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 97.3 57.0 39.7 25.2 16.6 13.6 11.6 7.33 6.23
1.80 103 59.9 41.6 26.3 17.3 14.1 12.0 7.60 6.45
1.75 106 61.4 42.6 26.8 17.6 14.4 12.2 7.69 6.52

 

 

back to top

 

 

UPS12-520MRX

 

UPS12-520MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-520 MRXF 884 666 525 437 338 283 255 239 209 147 153 AH 135 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 47.2 715 3586 3.50

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 737 574 458 388 307 260 236 223 197 139
1.70 793 609 480 403 315 265 240 227 199 141
1.67 831 626 493 412 320 269 243 229 200 141
1.65 859 637 503 419 324 271 245 231 202 142

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 784 611 487 412 324 273 248 233 205 145
1.70 843 648 511 428 333 279 252 237 207 146
1.67 884 666 525 437 338 283 255 239 208 147
1.65 914 678 535 444 342 285 257 241 210 148

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 92.4 52.2 36.7 23.6 15.7 13.0 11.1 7.09 6.05
1.80 97.8 54.9 38.6 24.7 16.4 13.5 11.5 7.35 6.26
1.75 101 56.3 39.5 25.2 16.7 13.8 11.7 7.46 6.35

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 96.3 54.2 38.1 24.4 16.2 13.3 11.4 7.28 6.21
1.80 102 57.1 40.0 25.5 16.9 13.9 11.8 7.54 6.42
1.75 105 58.5 40.9 26.1 17.2 14.1 12.0 7.65 6.52

 

 

back to top

 

 

UPS12-490MRX

 

UPS12-490MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-490 MRXF 794 624 495 411 317 265 239 224 195 141 149 AH 134 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 46.6 599 3160 3.96

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 653 527 423 357 282 240 218 206 182 133
1.70 708 567 450 377 294 284 225 212 186 135
1.67 747 587 465 388 300 252 227 214 187 135
1.65 776 605 475 395 304 254 229 216 188 136

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 695 561 449 379 298 252 229 216 190 139
1.70 753 603 479 400 311 261 236 222 194 140
1.67 794 624 495 411 317 265 239 224 195 141
1.65 825 643 506 419 321 267 241 226 196 141

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 87.8 49.7 35.7 23.4 15.8 13.0 11.0 6.91 5.86
1.80 93.3 52.4 37.4 24.4 16.4 13.4 11.4 7.15 6.05
1.75 94.6 52.9 38.0 25.0 16.8 13.7 11.6 7.29 6.16

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 91.5 51.6 36.9 24.2 16.3 13.3 11.3 7.09 6.01
1.80 97.2 54.4 38.7 25.2 16.9 13.8 11.7 7.33 6.21
1.75 98.5 55.0 39.4 25.8 17.3 14.1 11.9 7.47 6.32

 

 

back to top

 

UPS12-475MRX

 

UPS12-475MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-475 MRXF 784 622 475 385 286 237 213 199 172 120 115 AH 103 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 38 670 3350 3.77

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 684 541 415 341 260 218 197 186 163 113
1.70 713 568 432 354 267 223 201 189 164 114
1.67 737 585 447 362 271 225 203 190 165 115
1.65 743 596 450 366 273 227 204 192 166 115

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 728 575 441 362 275 230 207 194 169 118
1.70 759 604 460 375 282 234 210 197 171 119
1.67 784 622 475 385 286 237 213 199 172 120
1.65 790 634 479 388 289 239 214 200 173 120

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 78.2 42.0 29.2 18.5 12.1 9.96 8.45 5.33 4.52
1.80 82.3 44.1 30.6 19.3 12.6 10.4 8.77 5.52 4.68
1.75 83.1 45.1 31.3 19.7 12.8 10.5 8.92 5.60 4.74

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 81.5 43.6 30.3 19.1 12.5 10.2 8.67 5.47 4.64
1.80 85.7 45.8 31.7 19.9 13.0 10.6 9.00 5.66 4.80
1.75 86.6 46.9 32.4 20.3 13.2 10.8 9.15 5.74 4.86

 

 

back to top

 

UPS12-440MRX

 

UPS12-440MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-440 MRXF 719 552 436 355 266 223 201 189 165 117 121 AH 107 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 36 588 3183 3.96

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 640 490 388 320 244 205 186 175 154 110
1.70 662 506 401 329 249 210 190 179 157 112
1.67 676 519 410 335 252 212 192 181 158 112
1.65 686 528 415 339 254 214 193 182 159 113

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 680 521 412 339 258 216 195 183 160 115
1.70 704 538 427 349 263 220 199 187 163 116
1.67 719 552 436 355 266 223 201 189 165 117
1.65 729 562 442 360 269 225 203 190 166 118

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 74.8 42.7 29.9 19.0 12.5 10.3 8.72 5.52 4.68
1.80 77.8 44.0 30.8 19.6 13.0 10.7 9.12 5.80 4.93
1.75 79.7 44.9 31.5 20.0 13.2 10.9 9.27 5.88 5.00

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 78.0 44.4 31.0 19.6 12.9 10.5 8.95 5.66 4.80
1.80 81.0 45.8 31.9 20.3 13.4 11.0 9.35 5.94 5.06
1.75 83.0 46.6 32.7 20.7 13.6 11.2 9.51 6.03 5.13

 

 

back to top

 

 

UPS12-600MRX

 

UPS12-600MRX

Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 10 year design life @ 25°C
  • Absorbent Glass Mat (AGM) technology for
    efficient gas recombination of up
    to 99% and freedom from electrolyte
    maintenance.

  • 3 Year Warranty (refer Dynasty warranty
    card, 41-9027)
  • Patented Long Life Alloy having the
    lowest calcium levels in the industry -
    minimizing grid growth, reducing gassing,
    and extending battery life.

  • Patented UL Recognized Flamearresting
    vents in each cell for safety and
    long life.

  • Designed with the same recombination,
    thermal runaway prevention, gassing and
    flame retardant characteristics of the Bellcore
    4228 compliant Dynasty Telecom
    products.
  • Flame retardant polypropylene case and
    cover compliant with UL94V-2
  • Proprietary Fixed Orifice Plate Pasting
    technology applying active materials
    on both sides of the grid for consistent
    cell-to-cell performance, higher
    capacity and uniform grid protection.
  • Thermally welded case-to-cover bond to
    eliminate leakage.
  • Can be operated in any orientation.
    Upright, side or end mounting
    recommended.
  • Not restricted for air transport - Complies
    with IATA/ICAO Special Provisions A67.
  • Not restricted for surface transport -
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189.
  • Not restricted for water transport -
    Classified as non-hazardous material per
    IMDG Amendment 27.

 

 

TECHNICAL DATA

  Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C) 20 hour
rate to 1.75
VPC @
25°C
IEC Rating:10 hour rate
to 1.80 VPC
@ 20°C
Model Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 45 50 60 90
UPS 12-600 MRXF 969 745 601 486 361 299 268 251 217 153 147 AH 135 AH

 

Cells Per Unit Voltage Per Unit Weight
(Kg)
1 Min Current to 1.75VPC
(Amps)
Short Circuit Current
(Amps)
Internal Resistance
(mOhms)
6 12.98 49.4 828 3640 3.45

 

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23°C)to +80°F (27°C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1⁄4-20 UNC bolt.
Terminal Hardware
Initial Torque
110 in.-lbs. (12.4 N-m)

 

 

Dimensions

 

CONSTANT POWER DISCHARGE RATINGS

Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68 °F)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 816 641 518 427 326 274 247 233 204 145
1.70 872 681 548 447 336 280 252 237 206 146
1.67 911 700 565 458 342 284 255 239 208 147
1.65 939 710 572 463 345 287 257 241 209 148

 

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 868 682 551 453 345 288 259 244 212 151
1.70 928 725 583 475 355 295 265 248 215 152
1.67 969 745 601 486 361 299 268 251 217 153
1.65 999 756 608 492 365 302 270 253 218 154

 

CONSTANT CURRENT DISCHARGE RATINGS

Constant Current Discharge Ratings - Amperes @ 20°C (68 °F)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 94.1 53.0 37.5 24.3 16.0 13.0 11.0 6.76 5.70
1.80 99.7 55.8 39.3 25.4 16.6 13.5 11.4 7.06 6.95
1.75 102 56.8 40.2 25.8 16.9 13.8 11.6 7.18 6.05

 

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24
1.85 98.0 55.1 38.8 25.1 16.5 13.3 11.2 6.94 5.84
1.80 104 58.0 40.7 26.3 17.1 13.9 11.7 7.24 6.11
1.75 106 59.0 41.7 26.7 17.4 14.1 11.9 7.36 6.20

 

 

 

 

back to top