12_1029-MRXF

 

UPS 12-410 MRXF
UPS 12-615 MRXF
UPS 12-700 MRXF
UPS 12-1000 MRXF

 

Valve Regulated Lead A Design For UPS Stan Acid (VRLA) Battery Series dby Power Applications

 

APPLICATIONS FEATURES &
BENEFITS

  • Data Centers
  • Network Operations Centers
  • Industrial Process Control Facilities
  • Internet Housing Sites
  • Semiconductor Manufacturing
  • Banks & Financial Markets
  • Power Generation Plants
  • Hospitals & Testing Laboratories
  • Emergency 911 Response Centers

  • 12 years design life @ 25°C
  • True Front Acceess threaded
    copper alloy inserts, for reduced
    maintenance and increased safety

  • Terminal versatility - ease of diagnostic
    readings with C&D Ohmic Ring®
  • Innovative front terminal design
    maximizing energy density with
    direct connect extrusion fusion weld technology

  • Reduced headspace driving
    higher energy density, in cabinet
    or rack applicatiions

  • Removable handles
    for ease of installation
  • Thermally welded
    case-to-cover bond to ensure
    a leak-proof seal
  • Flame-retardant polypropylene
    case and covercompliant with
    UL94 V-0 with an Oxygen
    Limiting Index of greater than 28
  • Absorbent Glass Mat (AGM)
    technology for efficient gas
    recombination of over 99%
  • Flame-arresting, one-way
    pressure-relief vent for safety
    and long life
  • Complies with UL 1778,924,1989
    and 94 V-0. BS6290-4, IEC-896-2
  • UL-recognized component
  • Multicell design for ease of
    installation and maintenance
  • Not restricted for air transport -
    Complies with IATA/ICAO Special
    Provision A67
  • Not restricted for surface transport –
    Classified as non-hazardous material
    as related to DOT-CFR Title 49 parts
    171-189
  • 3 Year Full Warranty (refer to warranty card, 41-9027)
  • Not restricted for water transport –
    Classified as non-hazardous material
    IMDG Amendment 27

 

  Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25°C)
Model Voltage AH
20 hr*
Operating Time (in minutes) to 1.67 Volts per Cell
5 10 15 20 30 40 50 60 90
UPS 12-410 MRXF 12 109 701.1 514.6 410.0 339.5 256.0 203.1 169.8 146.6 105.1
UPS 12-615 MRXF 12 172 1027.1 771.8 615.0 513.8 392.5 318.8 271.3 237.8 171.5
UPS 12-700 MRXF 12 201 1117.8 866.0 700.0 583.0 453.0 368.1 313.3 247.7 199.3
UPS 12-1000MRXF 12 254 1520.0 1210.0 1000.0 823.7 616.2 491.2 412.0 356.9 256.7

 

*True 20 hr rate to 1.75 VPC in Ampere-hours

 

INTRODUCING A UPS FRONT ACCESS BATTERY WITH TRUE FRONT
ACCESS TERMINALS

  • Direct welded front facing terminals
  • – Uses proven Extrusion Fusion welding process s for high reliability

    – Provides most efficient current path for excelleent high rate performance

    – No bolted on “L” brackets which try to make a top terminals
    battery into a front terminal battery

    – One less bolted connection that requires maintenance,
    builds up resistance, and canlead to poor string performance

  • Designed as a UPS battery from the ground up to efficiently handle high rate discharges
  • –Not a converted telecom front access battery

  • Raised Terminals for ease of maintenance and access to C&D Ohmic Ring®

C&D Ohmic Ring®

  • Large surface area for direct access to terminals for accurate ohmic measurements
  • –No more taking readings from bus bars or hardware which can lead to substantial errors

  • Provides consistent and accurate measuring location
  • –No guessing to what point was the base line reading taken from

  • Ideally sized for use with standard i b flli lld monitor probes on fully installed systems
  • The Ohmic Ring design is the only terminal configuration in which micro-ohm connectio resistances can be taken as required by standard maintenance programs.

The True Front Access UPS Battery - The Better UPS Battery Solution

  • Eliminate hard to service top terminal BATTERIES & RECTIFIERS with a full front access solution
  • Higher watts per cell allows a reduction of a parallel string for most common UPS configurations,
    providing a reduced footprint solution
  • Maintenance is significantly easier and safer with all required service points front accessible -
    reducing both time and cost of periodic servicing
  • As a 12V battery design, the UPS12-410 MRXF,UPS12-615 MRXF and UPS12-700 MRXF easily
    integrate with existing battery monitoring equipment.

 

SPECIFICATIONS

Operating Temperature Range
with temperature compensation
Discharge: -40°F (-40°C) to +16°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range +74oF (23oC)to +80oF (27oC)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Float Charging Voltage 13.5 to 13.8 VDC average per 12V unit @ 77°F (25°C)
(Recommendation:13.65V per unit)
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. BATTERIES & RECTIFIERS stored at temperatures greater than 77°F (25°C)
will require recharge sooner than BATTERIES & RECTIFIERS stored at lower temperatures.
See C&D brochure 41-7272, Self-Discharge and I nventory Control for details.
Terminal: Inserted - Inter-unit
connector provided
Threaded copper alloy insert terminal to accept:
M6 bolt (UPS 12-410 MRXF)
M8 bolt (UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF)
Terminal Hardware
Initial Torque
107 in.-lbs ( 12 N-m) for UPS 12-410 MRXF
160 in.-lbs. ( 18 N-m) for UPS 12-615 MRXF, UPS 12-700 MRXF, UPS 12-1000 MRXF

 

 

Battery
Model
Voltage
Per Unit
Ampere Hours
Capacity 20 Hour Rate
@ 77°F (25°C) to
1.75EPV per cell
Ampere Hours
Capacity 10 Hour Rate
@ 68°F (20°C) to
1.80EPV per cell
IEC Short
Circuit
Current (A)
IEC
Resistance
(mOhms)
Weight
(kg)
UPS 12-410 MRXF 12V 109 100 2860 4.4 37.1
UPS 12-615 MRXF 12V 172 160 3700 3.4 55.2
UPS 12-700 MRXF 12V 201 185 4400 2.8 64.9
UPS 12-1000 MRXF 12V 254 234 5540 2.3 85.2

 

 

Battery
Model
Hioki
Impedance
(mOhms)
Midtronics
Cond. (Mhos)
Short Circuit
Current
(AMPS @0.1 sec)
Maximum
Terminal
Discharge Current
Rating (AMPS)
UPS 12-410 MRXF 2.37 2000 4900 800
UPS 12-615 MRXF 1.91 2500 6500 800
UPS 12-700 MRXF 1.84 2700 7900 800
UPS 12-1000 MRXF 1.47 3700 10100 1000

 

Per IEEE 1188-2005, Internal ohmic values are useful as a trending tool. To use these readings effectively, accurate baseline readings should be taken after about six months of battery operation. Internal ohmic readings taken without the benefit of baseline data may be difficult to interpret and of limited value. Values are provided are for reference only.

 

Dimensions

 


 

 

  A B C D E F G H
Model in mm in mm in mm in mm in mm in mm in mm in mm
UPS 12-410 MRXF 18.6 473.1 20.1 510.5 19.6 498.3 18.5 496.5 8.5 215.2 9.1 231.4 4.3 109.0 4.3 108.0
UPS 12-615 MRXF 20.3 516.9 22.0 558.5 21.5 546.5 20.2 512.2 10.6 268.9 11.0 278.7 4.9 125.0 4.9 123.4
UPS 12-700MRXF 20.3 516.9 22.0 558.5 21.5 546.5 20.2 512.2 12.2 310.8 12.7 322.1 4.9 125.0 4.9 123.4
UPS 12-1000MRXF 20.3 516.9 22.0 558.5 21.5 546.5 20.2 512.2 12.2 310.8 12.7 322.1 6.1 154.3 6.0 152.7

 

*All dimensions in inches and (millimeters). All dimensions are for reference only. Contact a C&D Representative for complete dimensions information.

 

Detail of Terminal

UPS 12 410 MRXF UPS 12-615 MRXF
UPS 12-700MRXF
UPS 12-1000 MRXF

 

back to top

 

UPS 12- 410 MRXF

Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 660.1 484.4 386.0 321.2 244.0 195.3 178.3 164.3 142.7 102.4
1.70 690.8 507.0 404.0 334.4 252.0 200.5 182.6 167.9 145.3 104.2
1.67 701.1 514.6 410.0 339.5 256.0 203.1 184.8 169.8 146.6 105.1
1.65 709.7 520.8 415.0 344.1 260.0 205.7 186.9 171.6 147.9 106.0

 

Constant Current Discharge Ratings - Amperes @ 77oF (25oC)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24 72
1.85 67 38.4 27.7 18.5 12.0 9.7 8.2 5.07 4.28 1.50
1.80 71 40.5 29.2 19.4 12.6 10.2 8.6 5.34 4.50 1.58
1.75 73 41 29.8 19.8 12.8 10.4 8.8 5.46 4.61 1.61

 

 

UPS 12-615 MRXF

Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 973.6 731.7 583.0 494.2 386.0 313.6 288.0 266.9 234.0 169.0
1.70 1010.4 759.3 605.0 508.0 391.0 317.4 269.9 236.9 236.5 170.7
1.67 1027.1 771.8 615.0 513.8 392.5 318.8 292.9 271.3 237.8 171.5
1.65 1035.4 778.1 620.0 516.8 393.5 319.5 293.4 271.8 238.2 172.0

 

Constant Current Discharge Ratings - Amperes @ 77oF (25oC)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24 72
1.85 109 61.8 44.0 28.7 19.0 15.5 13.1 8.10 6.81 2.38
1.80 118 65.8 46.7 30.4 20.1 16.3 13.8 8.47 7.12 2.49
1.75 120 67.0 47.5 30.9 20.3 16.5 13.9 8.61 726 2.54

 

Note: BATTERIES & RECTIFIERS to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

 

UPS 12-700 MRXF

Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 1020.6 780.0 630.0 544.1 437.0 358.7 330.8 307.7 271.5 196.5
1.70 1083.8 839.6 669.0 570.2 449.0 365.5 336.0 311.6 273.5 198.6
1.67 1117.8 866.0 700.0 583.0 453.0 368.1 338.1 313.3 274.7 199.3
1.65 1134.0 878.5 703.0 590.1 457.0 370.3 339.7 314.5 275.2 199.7

 

Constant Current Discharge Ratings - Amperes @ 77oF (25oC)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24 72
1.85 121 71.4 51.1 33.5 22.1 18.0 15.2 9.48 8.01 2.80
1.80 130 75.1 53.9 35.2 23.2 18.8 15.9 9.88 8.34 2.92
1.75 134 76.6 54.6 35.7 23.6 19.2 16.2 10.07 8.51 2.98

 

UPS 12-1000 MRXF

Constant Power Discharge Ratings - Watts Per Cell @ 77oF (25oC)
Operating Time to End Point Voltage ( in minutes)
End Point
Volts/CeIl
5 10 15 20 30 40 45 50 60 90
1.75 1379.8 1098.4 907.8 763.7 589.7 472.2 431.2 397.5 345.3 250.1
1.70 1469.0 1169.4 966.4 801.7 606.1 484.4 442.0 407.1 353.2 254.7
1.67 1520.0 1210.0 1000.0 823.7 616.2 491.2 447.7 412.0 356.9 256.7
1.65 1541.9 1227.5 1014.4 834.1 622.3 495.5 451.4 415.2 359.2 257.9

 

Constant Current Discharge Ratings - Amperes @ 77oF (25oC)
Operating Time to End Point Voltage ( in hours)
End Point
Volts/CeIl
1 2 3 5 8 10 12 20 24 72
1.85 168 96.1 67.9 43.2 28.1 22.9 19.4 12.05 10.18 3.56
1.80 181 102.0 71.3 45.0 29.3 23.9 20.2 12.50 10.60 3.71
1.75 188 104.1 72.1 45.4 29.7 24.3 20.6 12.70 10.70 3.75

 

Note: BATTERIES & RECTIFIERS to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

 

 

 