In environments that demand zero downtime, continuous power protection availability is essential. In order to respond to today’s dynamic IT and process-related environments that experience daily change through new server technologies, migration and centralization, resilient and easily adaptable power protection concepts are required.
CONCEPTPOWER DPA™ S2 is the foundation for continuous power protection availability of networkcritical infrastructures in enterprise data centers where business continuity has paramount importance and in process control environment where manufacturing continuity is essential.
NEWAVE CONCEPTPOWER DPA™ S2’S is a second generation high-power-density (HPD), leadingedge double-conversion power protection technology that has standardized on a modular component approach which helps speed deployment, improve adaptability and increase system availability while reducing total cost of ownership.
CONCEPTPOWER DPA™ S2’S is a unique on-demand architecture that integrates the power rack, power distribution unit, back-up battery rack and monitoring and management solutions to allow easy selection of optimized configurations.
CONCEPTPOWER DPA™ S2’S (Distributed Parallel Architecture) provides highest availability, unmatched flexibility and at the same time lowest cost of ownership in IT environments.
This Technical Specification provides detailed technical information on the mechanical, electrical and environmental performance of the CONCEPTPOWER DPA™ S2 that can support to give answers to tender and end-user requirements. The CONCEPTPOWER DPA™ S2 was designed to respond to the most stringent safety, EMC and other important UPS standards.
CONCEPTPOWER DPA™ S2 is a rack-mountable modular design. It offers 3-types of Racks (Frames) and 3 types of DPA-Modules to accommodate a wide range of power requirements.
The three MX-Frames; Classic DPA-50, Triple DPA-150, Upgrade DPA-250 can accommodate the three (3) MX-DPA-Modules types DPA 30 or 40 or 50 of: 30kVA/24kW - 40kVA/32kW - 50kVA/40kW power.
|
Near-zero down time |
|
Space-saving of expensive floor space |
|
No de-rating with leading PF loads |
|
Energy cost saving during UPS-life-cycle |
|
Gen-set power and installation cost saving |
CONCEPTPOWER DPA | CLASSIC DPA-50 | TRIPLE DPA-150 | UPGRADE DPA-250 | |
MX - FRAMES | ![]() |
![]() |
![]() |
|
Configuration accommodates: |
Max. |
1 module (30-50kVA) and 280 x 7/9Ah BATTERIES & RECTIFIERS |
3 modules (30-50kVA) and 240x 7/9Ah BATTERIES & RECTIFIERS |
5 modules (30-50kVA) and no BATTERIES & RECTIFIERS |
Max. Power connection | kVA | 50 | 150 | 250 |
Dimensions (WxHxD) | mm | 730x1650x800 | 730x1975x800 | 730x1975x800 |
Weight of Empty Frame w/o modules and w/o BATTERIES & RECTIFIERS |
kg |
262 |
239 |
205 |
Weight of Frame with modules and w/o BATTERIES & RECTIFIERS |
kg |
305 up to 309 (with 1 Module) |
368 up to 379 (with 3 Modules) |
420 up to 439 (with 5 Modules) |
Colours |
Front door silver :RAL 9007 + NEWAVE black (inlets) Side walls/top: Graphite grey (Pulverlacke No. 4222903402 serie 09RCCAT1) |
MX- DPA MODULES | ![]() |
DPA 30 S2 |
DPA 40 S2 |
DPA 50 S2 |
Output Apparent Rated Power |
KVA |
30 |
40 |
50 |
Output Active Rated Power |
KW |
24 |
32 |
40 |
Output Power with Load PF=1 |
KVA / KW |
24 / 24 |
32 / 32 |
40 /40 |
Variable Number of 12V Battery Blocks |
No. |
40-50 |
40-50 |
40-50 |
Dimensions (WxHxD) |
mm |
663 x 225 x 720 |
||
Weight UPS Module |
kg |
43.1 |
45.3 |
46.8 |
Colours |
Front : Graphite grey
(Pulverlacke No. 4222903402 serie 09RCCAT1) |
Module Range |
MX |
|||
Module Type |
DPA 30 S2 |
DPA 40 S2 |
DPA 50 S2 |
|
Output Rated Power per Module cosφ 0.8 |
kVA |
30 |
40 |
50 |
Output Rated Power per Module cosφ 1.0 |
KW |
24 |
32 |
40 |
Nominal Input Voltage |
V |
3x380/220V+N, 3x400V/230V+N, 3x415/240V+N |
||
Input Voltage Tolerance
(ref to 3x400/230V) for Loads in %: |
V |
(-23%/+15%) 3x308/177 V to 3x460/264 V for <100 % load (-30%/+15%) 3x280/161 V to 3x460/264 V for < 80 % load (-40%/+15%) 3x240/138 V to 3x460/264 V for < 60 % load |
||
Input Frequency |
Hz |
30 - 70 |
||
Input Power Factor |
PF=0.99 @ 100 % load |
|||
Inrush Current |
A |
limited by soft start / max. In |
||
Input Distortion THDI |
Sine-wave THDi = < 3 % @ 100% load |
|||
Max. Input Power with rated output power and charged battery per Module (output Cosφ = 1.0) |
kW |
25.5 |
34.0 |
42.6 |
Max. Input Current with rated output power and charged battery per Module (output Cosφ = 1.0) |
A |
36.8 |
49.1 |
62.1 |
Max. Input Power with rated output power and discharged battery per Module (output Cosφ = 1.0) |
kW |
28.1 |
37.4 |
46.8 |
Max. Input Current with rated output powe and discharged battery per Module (output Cosφ = 1.0) |
A |
40.7 |
54.2 |
67.8 |
Module Range |
MX |
|||
Module Type |
DPA 30S2 |
DPA 40 S2 |
DPA 50 S2 |
|
Variable Number of 12V Battery Blocks |
No. |
40-50 |
40-50 |
40-50 |
Maximum Battery Charger Current |
A |
10A Standard |
||
Battery Charging Curve |
Ripple free ; IU (DIN 41773) |
|||
Temperature compensation |
Standard (temp. sensor optional) |
|||
Battery Test |
Automatic and periodically (adjustable) |
|||
Battery Type |
Maintenance free VRLA or NiCd |
|||
On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW |
Module Range |
MX |
|||
Module Type |
DPA 30 S2 |
DPA 40 S2 |
DPA 50 S2 |
|
Output Rated Power per Module |
kVA |
30 |
40 |
50 |
Output Rated Power per Module |
KW |
24 |
32 |
40 |
Output Current In @ cosphi 1.0 (400 V) |
kVA |
35 |
46.5 |
58 |
Output Rated Voltage |
V |
3x380/220V or 3x400/230V or 3x415/240V |
||
Output Voltage Stability |
% |
Static: < ± 1% Dynamic (Step load 0%-100% or 100%-0%) < ± 4% |
||
Output Voltage Distortion |
% |
With Linear Load < 2% With Non-linear Load (EN62040-3) < 4% |
||
Output Frequency |
Hz |
50 Hz or 60 Hz |
||
Output Frequency Tolerance |
% |
Synchronized with mains < ± 2 % (selectable for bypass operation) or < ± 4 % Free running ± 0.1 % |
||
Bypass operation |
At Nominal Input voltage of 3x400 V +/- 15% or 196 V to 264 V ph-N |
|||
Permissible Unbalanced Load (All 3 phases regulated independently) |
% |
100% | ||
Phase Angle Tolerance (With 100 % Unbalanced load) |
Deg. |
± 0 deg. | ||
Overload Capability on Inverter |
% |
125 % load 10 min. 150 % load 60 sec. |
||
Output short capability (RMS) |
A |
Inverter : up to 3 x In during 40 ms Bypass : 10 x In during 10 ms |
||
Crest - Factor |
3 : 1 |
cosφ |
MX Module Range |
||||||
DPA30 S2 |
DPA40 S2 |
DPA50 S2 |
|||||
kW |
kVA |
kW |
kVA |
kW |
kVA |
||
Cap. | 0.85 | 18.5 | 21.8 | 24.6 | 29 | 31 | 36.5 |
0.90 | 24 | 26.7 | 32 | 35.6 | 40 | 44.4 | |
0.95 | 24 | 25.3 | 32 | 33.7 | 40 | 42.1 | |
Ind. | 1.00 | 24 | 24 | 32 | 32 | 40 | 40 |
0.95 | 24 | 25.3 | 32 | 33.7 | 40 | 42.1 | |
0.90 | 24 | 26.7 | 32 | 35.6 | 40 | 44.4 | |
0.85 | 24 | 28.2 | 32 | 37.6 | 40 | 47.1 | |
0.80 | 24 | 30 | 32 | 40 | 40 | 50 | |
0.75 | 22.9 | 30 | 30.5 | 40 | 38 | 50 | |
0.70 | 21.7 | 30 | 28.9 | 40 | 36 | 50 | |
0.60 | 19 | 30 | 25.4 | 40 | 32 | 50 |
Module Range |
MX |
|||
Module Type |
DPA 30 S2 |
DPA 40 S2 |
DPA 50 S2 |
|
Audible Noise with 100% / 50% Load |
dBA |
64/55 |
65/56 |
65/56 |
Operation temperature |
°C |
0 – 40 |
||
Ambient Temperature for BATTERIES & RECTIFIERS (recommended) |
°C |
20 – 25 |
||
Storage Temperature |
°C |
-25 – +70 |
||
Battery Storage Time at Ambient Temperature |
Max. 6 months |
|||
Max. altitude (above sea level) |
m |
1000m (3300ft) without de-rating |
||
De-rating factor for use at altitudes above 1000m sea level according ( IEC 62040-3) |
Meter above sea level (m / ft) 1500 / 4850 2000 / 6600 2500 / 8250 3000 / 9900 |
De-Rating Factor for Power 0.95 0.91 0.86 0.82 |
||
Relative Air-humidity |
Max. 95% (non-condensing) |
|||
Accessibility |
Totally front accessibility for service and maintenance (no need for side, top or rear access) |
|||
Positioning |
Min. 20 cm rear space (required for fan) |
|||
Input and Output Power Cabling |
From the bottom on the front |
|||
Efficiency AC-AC up to (at cosphi 1.0) (depending on Module power) |
% |
Load : 100% 75% 50% 25% |
||
DPA 30-50: 95.2% 95.5% 95.7% 94.5% |
||||
Efficiency Non-linear Load (EN 62040-1-1:2003) |
Typically up to 1 % lower of above values |
|||
Eco-Mode efficiency at 100% load | % |
98% |
Safety |
Product Standards IEC/EN 62040-1 |
Standards IEC/EN 60950-1 |
|
Electromagnetic Compatibility |
Product Standards IEC/EN 62040-2 |
Standards IEC/EN 61000-6-2 ; IEC/EN 61000-6-4 |
|
EMC Classification |
DPA-30 |
DPA-40 |
DPA-50 |
Emission Class |
C2 |
C2 |
C2 |
Immunity Class |
C3 |
C3 |
C3 |
Performance |
IEC/EN 62040-3 |
||
Product certification |
CE |
||
Degree of protection |
IP 20 |
Power Management Display (PMD) | 1 LCD display for each module |
Serial ports RS232 on Sub-D9 |
2x system frame + 1x on each module (Smart Port) For monitoring and integration in network management |
USB | 1x For monitoring and software management |
Customer Interfaces : Inputs DRY PORT X1 |
1 Remote Shut down [EMERGENCY OFF (Normally closed)] 1 GEN-ON (Normally open) 2 Programmable Customer’s Inputs (Normally open) 1 Temp. Sensor for Battery Control |
Customer Interfaces : Outputs DRY PORT X2 , X3, X4 |
10 voltage free contacts For remote signalling and automatic computer shutdown |
Slot for SNMP |
SNMP card (optional) For monitoring and integration in network management |
The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides the necessary monitoring information about the UPS
The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the corresponding LEDindicators will change colour from green (normal) to red (warning). The LED’s LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s INVERTER and BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time the audible alarm will be activated.
The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer from INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for adjustments and testing (for more details see the USER MANUAL of Conceptpower DPATM S2).
Power Management Display (PMD) of Conceptpower DPM TM S2
Connection of Remote Shut down facilities, Generator Operation, Customers specials (see UM Section 9 / OPTIONS)
Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm2
Phoenix Spring Terminals (X1…X4) Connection
The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-protocol. It is used to monitor any device in the network via simple control language. The UPS-Management Software WaveMon also provides its data in this SNMP format with its internal software agent. The operating system you are using must support the SNMP protocol. We offer our WaveMon software with SNMP functionality for Novell, OS/2, all Windows running on INTEL and ALPHA, DEC VMS, Apple.
Two types of SNMP interfaces with identical functionality are available: an external SNMP-Adapter (Box) and an internal SNMP-Card. Both can manage a parallel system (N modules) and return either global values - which are consistent for the whole parallel system - or specific values from the single modules.
S-type = For Separate. Battery C-type = For Common. Battery |
CBAT-DPA-120 S-type or C-type |
CBAT-DPA-200 S-type or C-type |
|
BATTERY FRAMES | ![]() |
![]() |
|
Configuration accommodates: | Max. |
120 Batt. block x 24Ah/28Ah on 8 shelf 3x5=15 blocks/shelf |
200 Batt. blocks x 24Ah/28Ah on 7 shelf 6x5=30 blocks/shelf |
Battery fuses / Max. Batt. Strings : Terminals : |
S-type |
3 / 3 (Terminal 9 x 16/25mm2) |
5 / 5 (Terminal 15 x 16/25mm2) |
Battery fuses / Max. Batt. Strings Terminals : |
C-type |
3 / 3 + Com. Connection Bar 3 x (2xM8) +PE 2xM8 |
5 / 5 + Com. Connection Bar 3 x (2xM10) +PE 2xM10 |
Fuse Type (Very Fast acting) |
A |
3x100 A |
5x100 A |
Dimensions (WxHxD) |
mm |
730x1975x800 |
1200x1975x800 |
Weight with trays and w/o BATTERIES & RECTIFIERS |
kg |
290 |
410 |
Possible Battery configurations within the Battery Cabinets |
Battery Configurations 30x28Ah
40x28Ah
50x28Ah
(2x30)x28Ah
(2x40)x28Ah
(2x50)x28Ah
(3x30)x28Ah
(3x40)x28Ah
|
Battery Configurations (2x40)x28Ah (3x40)x28Ah (4x40)x28Ah (5x40)x28Ah (2x50)x28Ah (3x50)x28Ah (4x50)x28Ah (5x30)x28Ah (5x40)x28Ah |
Module Type | DPA 30 | DPA 40 | DPA 50 | |
Separate Battery configuration |
Battery Autonomy in (min.) per Module |
|||
Frame Type |
Battery / Module (up to 3 modules / within Triple-150 frame) |
30kVA/24KW |
40KVA/32KW |
50KVA/40KW |
CLASSIC DPA-50 or TRIPLE DPA-150 |
(2x40)x9Ah |
8 |
6 |
|
Common Battery configuration |
Battery Autonomy in (min.) for Tot. System Power |
|||
With 1 Module |
Module Type Total System Power |
1 x DPA 30 30kVA/24KW |
1 x DPA 40 40KVA/32KW |
1 x DPA 50 50KVA/40KW |
CLASSIC DPA-50 | (2x50)x9Ah |
11 |
8 |
|
CLASSIC DPA-50 | (3x40)x9Ah |
14 |
9 |
|
CLASSIC DPA-50 | (3x50)x9Ah |
18 |
13 |
9 |
CLASSIC DPA-50 | (4x50)x9Ah |
26 |
18 |
14 |
CLASSIC DPA-50 | (5x50)x9Ah |
34 |
24 |
18 |
With 2 Modules |
Module Type 2 Total System Power |
x DPA 30 2 60kVA/48KW |
x DPA 40 80kVA/64KW |
2 x DPA 50 100kVA/80KW |
TRIPLE DPA-150 | 2x(2x40)x9Ah |
8 |
||
TRIPLE DPA-150 | 3x(2x40)x9Ah |
14 |
9 |
7 |
With 3 Modules |
Module Type Total System Power |
3 x DPA 30 90kVA/72KW |
3 x DPA 40 120kVA/96KW |
3 x DPA 50 150kVA/120KW |
TRIPLE DPA-150 | 3x(2x40)x9Ah |
8 |
6 |
|
This configuration are mostly used in combination with the frame UPGRADE DPA-250
Module Type | DPA 30 | DPA 40 | DPA 50 | |
Separate Battery configuration |
Battery Autonomy in (min.) per Module |
|||
Battery Cabinet (for up to 5 modules linked) |
Battery / Module |
30kVA/24KW |
40KVA/32KW |
50KVA/40KW |
1x CBAT-DPA-200 | 40x28Ah |
13 |
9 |
7 |
Common Battery configuration |
Battery Autonomy in (min.) for Tot. System Power (4+1) |
|||
With 4 Modules |
Module Type Total System Power |
4 x DPA 30 120kVA/96KW |
4 x DPA 40 160kVA/128KW |
4 x DPA 50 200kVA/160KW |
1x CBAT-DPA-120 | (3x40)x28Ah |
9 |
6 |
|
1x CBAT-DPA-200 | (3x50)x28Ah |
12 |
9 |
|
1x CBAT-DPA-200 | (4X50)x28Ah |
18 |
12 |
9 |
2x CBAT-DPA-200 | 5x (2x40) x 28Ah |
43 |
30 |
22 |
UPS Frame type (50kVA up to 250 kVA) | CLASSIC DPA-50 | TRIPLE DPA-150 | UPGRADE DPA-250 |
Dimensions (WxHxD) mm | 730x1650x800 | 730x1975x780 | 730x1975x800 |
Battery Cabinet Type | NA | CBAT DPA-120 | CBAT DPA-200 |
Dimensions (WxHxD) mm | NA | 730x1975x800 | 1200x1975x800 |
Accessibility | Totally front accessibility for service and maintenance (no need for side, top or rear access) | ||
Positioning Min. | 20 cm rear space (required for fan) | ||
Input and Output Power Cabling | From the bottom on the front |
Module size |
MX |
|||
Module Type |
DPA 30 S2 |
DPA 40 S2 |
DPA 50 S2 |
|
Heat Dissipation with 100% Non-linear Load per Module (EN 62040-1-1:2003) |
W |
1532 |
2043 |
2553 |
Heat Dissipation with 100% Non-linear Load per Module (EN 62040-1-1:2003 |
BTU |
5227 |
6969 |
8712 |
Airflow (25° - 30°C) with Non-linear Load per Module (EN 62040-1-1:2003) |
m3/h |
380 |
380 |
380 |
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such as a licensed service engineer from the manufacturer or from an agent authorised by the manufacturer. More details and procedure are mentioned in the user manual.
FRAME TYPE Terminals (T) Connection Bar (B) |
Separate. Battery (+ / N / - ) +PE |
Common Battery (+ / N / - ) +PE |
Input Bypass 3+N |
Input Rectifier 3+N+PE |
Output load 3+N+PE |
CLASSIC DPA-50 | 3+1 x 16/25mm2 (T) | 3+1 x 16/25mm2 (T) | 4 x 16/25mm2 (T) | 5 x 16/25mm2 (T) | 5 x 16/25mm2 (T) |
TRIPLE DPA-150 |
9+1 x 16/25mm2 (T) +PE 1xM10 (B) |
3 x M10 (B) +PE 1xM10 (B) |
3 x M10(B) +PE 1xM10 (B) |
4 x M10 (B) +PE 1xM10 (B) |
4 x M10 (B) +PE 1xM10 (B) |
UPGRADE DPA-250 |
15 x 16/25mm2 (T) +PE 1xM12 (B) |
3 x M12 (B) +PE 1xM12 (B) |
3 x M12 (B) +PE 1xM12 (B) |
4 x M12 (B) +PE 1xM12 (B) |
4 x M12 (B) +PE 1xM12 (B) |
![]() |
![]() |
![]() |
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Frame type |
Load kVA cosphi 0.8 |
Input 3x400V | Output 3x400V cosphi 0.8 | Battery | |||||
Fuse A (Agl/CB) |
Cable A (mm2) (IEC 60950-1) |
Max. Input Current with battery c harging (A) |
Cable D (mm2) (IEC 60950-1) |
I nom (A) |
Fuse E + / N / - (Agl/CB) |
Cable E (mm2) for CBAT DPA 120 or 200 ONLY + / N / - |
|||
Com. Battery | Sep. Battery | ||||||||
MX Frames (Frames shall be cabled to there full rating capability) | |||||||||
CLASSIC DPA 50 | 50 | 3x100A | 5x25 | 67 | 5x25 | 72 A | 3x100A*1 | 3x25 | 3x25 |
TRIPLE DPA-150 | 150 | 3x250A | 5x120 or 5x(2x50) | 202 | 5x120 or 5x(2x50) | 218 A | 3x300A*1 | 3x150 | 3x(3x25) |
UPGRADE DPA-250 | 250 | 3x400A | 5x(2x95) | 337 | 5x(2x95) | 362 A | 3x500A*1 | 3x(2x150) | 5x (3x25) |
Other intermediate Ratings (we recommend to cable the frame mentioned above at full rating to able future upgrading) | |||||||||
30 | 3x63A | 5x10 | 40 | 5x10 | 43 A | 3x80A | 3x16 | ||
40 | 3x80A | 5x25 | 54 | 5x25 | 58 A | 3x100A* | 3x25* | ||
45 | 3x100A | 5x25 | 68 | 5x25 | 65 A | 3x125A* | 3x35* | ||
60 | 3x100A | 5x25 | 81 | 5x25 | 87 A | 3x125A* | 3x35* | ||
80 | 3x125A | 5x50 | 108 | 5x50 | 116 A | 3x160A* | 3x50* | ||
90 | 3x160A | 5x50 | 121 | 5x50 | 130 A | 3x200A* | 3x70* | ||
100 | 3x160A | 5x50 | 135 | 5x50 | 145 A | 3x224A* | 3x95* | ||
120 | 3x200A | 5x70 | 161 | 5x70 | 174 A | 3x250A* | 3x120* | ||
160 | 3x250A | 5x120 or 5x(2x50) | 215 | 5x120 or 5x(2x50) | 232 A | 3x350A* | 3x(2x70)* | ||
200 | 3x315A | 5x185 or 5x(2x70) | 267 | 5x185 or 5x(2x70) | 290 A | 3x450A* | 3x(2x95)* |
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Frame Type |
Load kVA cosphi 0.8 |
Input 3x400V | Bypass 3x400V | Output 3x400V cosphi 0.8 | Battery | ||||||
Fuse B (Agl/CB) |
Cable B (mm2) (IEC 60950-1) |
Max. Input Current with battery c harging (A) |
Fuse C (Agl/CB) |
Cable |
Cable D (mm2) (IEC 60950-1) |
I nom (A) |
Fuse E + / N / - (Agl/CB) |
Cable E (mm2) for CBAT DPA 120 or 200 ONLY + / N / - |
|||
Com. Battery | Sep. Battery | ||||||||||
MX Frames (Frames shall be cabled to there full rating capability) | |||||||||||
CLASSIC DPA 50 | 50 | 3x100A | 5x25 | 67 | 3x100A | 4x25 | 5x25 | 72 A | 3x100A*1 | 3x25 | 3x25 |
TRIPLE DPA-150 | 150 | 3x250A | 5x120 or 5x(2x50) | 202 | 3x250A | 4x120 or 4x(2x50) |
5x120 or 5x(2x50) |
218 A | 3x300A*1 | 3x150 | 3x (3x25) |
UPGRADE DPA-250 | 250 | 3x400A | 5x(2x95) | 337 | 3x400A | 4x(2x95) | 5x(2x95) | 362 A | 3x500A*1 | 3x(2x150) | 5x (3x25) |
Other intermediate Ratings (we recommend to cable the frame mentioned above at full rating to able future upgrading) | |||||||||||
30 | 3x63A | 5x10 | 40 | (3x25) | 4x10 | 5x10 | 43 A | 3x80A | 3x16 | ||
40 | 3x80A | 5x25 | 54 | 3x80A | 4x25 | 5x25 | 58 A | 3x100A* | 3x25* | ||
45 | 3x100A | 5x25 | 68 | 3x100A | 4x25 | 5x25 | 65 A | 3x125A* | 3x35* | ||
60 | 3x100A | 5x25 | 81 | 3x100A | 4x25 | 5x25 | 87 A | 3x125A* | 3x35* | ||
80 | 3x125A | 5x50 | 108 | 3x125A | 4x50 | 5x50 | 116 A | 3x160A* | 3x50* | ||
90 | 3x160A | 5x50 | 121 | 3x160A | 4x50 | 35x50 | 130 A | 3x200A* | 3x70* | ||
100 | 3x160A | 5x50 | 135 | 3x160A | 4x50 | 5x50 | 145 A | 3x224A* | 3x95* | ||
120 | 3x200A | 5x70 | 161 | 3x200A | 4x70 | 5x70 | 174 A | 3x250A* | 3x120* | ||
160 | 3x250A | 5x120 or 5x(2x50) | 215 | 3x250A | 4x120 or 4x(2x50) |
5x120 or 5x(2x50) |
232 A | 3x350A* | 3x(2x70)* | ||
200 | 3x315A | 5x185 or 5x(2x70) | 267 | 3x315A | 4x185 or 4x(2x70) |
5x185 or 5x(2x70) |
290 A | 3x450A* | 3x(2x95)* |