Conceptpower DPA S2 Technical Specifications

Conceptpower DPA S2 highlights at a glance


  • DPA with Safe-Swap Modules (SSM) For premium power protection availability
  • Low total Cost of Ownership (TCO) Cost saving during entire life-cycle
  • Flexibility/Scalability Ease of power upgrade, pay as you grow
  • Enhanced Serviceability Rapid fault recovery

Conceptpower DPA S2 system description

In environments that demand zero downtime, continuous power protection availability is essential. In order to respond to today’s dynamic IT and process-related environments that experience daily change through new server technologies, migration and centralization, resilient and easily adaptable power protection concepts are required.

CONCEPTPOWER DPA™ S2 is the foundation for continuous power protection availability of networkcritical infrastructures in enterprise data centers where business continuity has paramount importance and in process control environment where manufacturing continuity is essential.

NEWAVE CONCEPTPOWER DPA™ S2’S is a second generation high-power-density (HPD), leadingedge double-conversion power protection technology that has standardized on a modular component approach which helps speed deployment, improve adaptability and increase system availability while reducing total cost of ownership.

CONCEPTPOWER DPA™ S2’S is a unique on-demand architecture that integrates the power rack, power distribution unit, back-up battery rack and monitoring and management solutions to allow easy selection of optimized configurations.

CONCEPTPOWER DPA™ S2’S (Distributed Parallel Architecture) provides highest availability, unmatched flexibility and at the same time lowest cost of ownership in IT environments.

This Technical Specification provides detailed technical information on the mechanical, electrical and environmental performance of the CONCEPTPOWER DPA™ S2 that can support to give answers to tender and end-user requirements. The CONCEPTPOWER DPA™ S2 was designed to respond to the most stringent safety, EMC and other important UPS standards.

CONCEPTPOWER DPA™ S2 is a rack-mountable modular design. It offers 3-types of Racks (Frames) and 3 types of DPA-Modules to accommodate a wide range of power requirements.

The three MX-Frames; Classic DPA-50, Triple DPA-150, Upgrade DPA-250 can accommodate the three (3) MX-DPA-Modules types DPA 30 or 40 or 50 of: 30kVA/24kW - 40kVA/32kW - 50kVA/40kW power.

Key Features of CONCEPTPOWER DPA S2 Modules:


  • Highest Availability

    Modular, Decentralized Parallel Architecture (DPA)

 Near-zero down time
  • High Power Density (up to 342kW / m2)

    Small Footprint

 Space-saving of expensive floor space
  • Blade-server-friendly power

    Full power from 0.9 lead to 0.8 lag

 No de-rating with leading PF loads
  • Highest Efficiency even with partial loads

    Efficiency up to 95.7% (depending on Module power and type of load)

 Energy cost saving during UPS-life-cycle
  • Very low input current distortion THDi

    THDi = < 3 - 4% for loads of 100 – 25 %

 Gen-set power and installation cost saving

Technical Characteristics

Mechanical Characteristics MX-frames and modules

 CONCEPTPOWER DPA    CLASSIC DPA-50  TRIPLE DPA-150  UPGRADE DPA-250
 MX - FRAMES   Classic DPA 50 Triple DPA 150 Upgrade DPA 250
 

Configuration

accommodates:

 Max.  

1 module

(30-50kVA) and

280 x 7/9Ah BATTERIES & RECTIFIERS

 

3 modules

(30-50kVA) and

240x 7/9Ah BATTERIES & RECTIFIERS

 

5 modules

(30-50kVA) and

no BATTERIES & RECTIFIERS

 Max. Power connection  kVA  50  150  250
 Dimensions (WxHxD)  mm  730x1650x800  730x1975x800  730x1975x800
 

Weight of Empty

Frame

w/o modules and

w/o BATTERIES & RECTIFIERS

 kg  
262
 
239
 
205
 

Weight of Frame

with modules and

w/o BATTERIES & RECTIFIERS

 kg  

305 up to 309

(with 1 Module)

 

368 up to 379

(with 3 Modules)

 

420 up to 439

(with 5 Modules)

 Colours    

Front door silver :RAL 9007 + NEWAVE black (inlets)

Side walls/top: Graphite grey (Pulverlacke No. 4222903402 serie 09RCCAT1)


 MX- DPA MODULES
mx-dpa-modules
 
DPA 30 S2
 
DPA 40 S2
 
DPA 50 S2
 Output Apparent Rated Power  
KVA
 
30
 
40
 
50
 Output Active Rated Power  
KW
 
24
 
32
 
40
 Output Power with Load PF=1  
KVA / KW
 
24 / 24
 
32 / 32
 
40 /40
 Variable Number of 12V Battery Blocks  
No.
 
40-50
 
40-50
 
40-50
 Dimensions (WxHxD)  
mm
 
663 x 225 x 720
 Weight UPS Module  
kg
 
43.1
 
45.3
 
46.8
 Colours    
Front : Graphite grey

(Pulverlacke No. 4222903402 serie 09RCCAT1)


Power Selection Table Conceptpower DPA Modules

Concept Power DPA: Power Modules DPA 30 - DPA 50


Go to the top

Input Characteristics

 Module Range  
MX
 Module Type  
DPA 30 S2
 
DPA 40 S2
 
DPA 50 S2
 Output Rated Power per Module cosφ 0.8  
kVA
 
30
 
40
 
50
 Output Rated Power per Module cosφ 1.0  
KW
 
24
 
32
 
40
 Nominal Input Voltage  
V
 
3x380/220V+N,         3x400V/230V+N,         3x415/240V+N
 Input Voltage Tolerance

(ref to 3x400/230V) for Loads in %:

 
V
 

(-23%/+15%) 3x308/177 V to 3x460/264 V for <100 % load

(-30%/+15%) 3x280/161 V to 3x460/264 V for < 80 % load

(-40%/+15%) 3x240/138 V to 3x460/264 V for < 60 % load

 Input Frequency  
Hz
 
30 - 70
 Input Power Factor    
PF=0.99 @ 100 % load
 Inrush Current  
A
 
limited by soft start / max. In
 Input Distortion THDI    
Sine-wave THDi = < 3 % @ 100% load
 Max. Input Power with rated output power and charged battery per Module (output Cosφ = 1.0)  
kW
 
25.5
 
34.0
 
42.6
 Max. Input Current with rated output power and charged battery per Module (output Cosφ = 1.0)  
A
 
36.8
 
49.1
 
62.1
 Max. Input Power with rated output power and discharged battery per Module (output Cosφ = 1.0)  
kW
 
28.1
 
37.4
 
46.8
 Max. Input Current with rated output powe and discharged battery per Module (output Cosφ = 1.0)  
A
 
40.7
 
54.2
 
67.8

Input PF versus % load


input-power-factor

Input Distortion THDI versus % load


input-current-distortion


Battery Characteristics

 Module Range  
MX
 Module Type  
DPA 30S2
 
DPA 40 S2
 
DPA 50 S2
 Variable Number of 12V Battery Blocks  
No.
 
40-50
 
40-50
 
40-50
 Maximum Battery Charger Current  
A
 
10A Standard
 Battery Charging Curve  
Ripple free ; IU (DIN 41773)
 Temperature compensation  
Standard (temp. sensor optional)
 Battery Test  
Automatic and periodically (adjustable)
 Battery Type  
Maintenance free VRLA or NiCd
 On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW

Output Characteristics

 Module Range  
MX
 Module Type  
DPA 30 S2
 
DPA 40 S2
 
DPA 50 S2
 Output Rated Power per Module  
kVA
 
30
 
40
 
50
 Output Rated Power per Module  
KW
 
24
 
32
 
40
 Output Current In @ cosphi 1.0 (400 V)  
kVA
 
35
 
46.5
 
58
 Output Rated Voltage  
V
 
3x380/220V       or 3x400/230V or       3x415/240V
 Output Voltage Stability  
%
 

Static:  < ± 1%

Dynamic (Step load 0%-100% or 100%-0%)   < ± 4%

 Output Voltage Distortion  
%
 

With Linear Load   < 2%

With Non-linear Load (EN62040-3)   < 4%

 Output Frequency  
Hz
 
50 Hz or 60 Hz
 Output Frequency Tolerance  
%
 

Synchronized with mains   < ± 2 %

(selectable for bypass operation)   or < ± 4 %

Free running   ± 0.1 %

 Bypass operation    

At Nominal Input voltage of 3x400 V +/- 15%

or 196 V to 264 V ph-N

 

Permissible Unbalanced Load

(All 3 phases regulated independently)

 
%
 100%
 

Phase Angle Tolerance

(With 100 % Unbalanced load)

 
Deg.
 ± 0 deg.
 Overload Capability on Inverter  
%
 

125 % load   10 min.

150 % load   60 sec.

 Output short capability (RMS)  
A
 

Inverter :  up to 3 x In during  40 ms

Bypass :  10 x In during  10 ms

 Crest - Factor    
3 : 1

AC – AC EFFICIENCY with Linear load @ cosphi 1

linear-load


Output Power in KW and KVA VERSUS cosphi

dpa-50-output-power

Go to the top

AC-AC Efficiency of DPA 50 Module


   
cosφ
 
MX Module Range
 
DPA30 S2
 
DPA40 S2
 
DPA50 S2
 
kW
 
kVA
 
kW
 
kVA
 
kW
 
kVA
 Cap.  0.85  18.5  21.8  24.6  29  31  36.5
 0.90  24  26.7  32  35.6  40  44.4
 0.95  24  25.3  32  33.7  40  42.1
 Ind.  1.00  24  24  32  32  40  40
 0.95  24  25.3  32  33.7  40  42.1
 0.90  24  26.7  32  35.6  40  44.4
 0.85  24  28.2  32  37.6  40  47.1
 0.80  24  30  32  40  40  50
 0.75  22.9  30  30.5  40  38  50
 0.70  21.7  30  28.9  40  36  50
 0.60  19  30  25.4  40  32  50


Environmental Characteristics

 

 Module Range    
MX
 Module Type    
DPA 30 S2
 
DPA 40 S2
 
DPA 50 S2
 

Audible Noise

with 100% / 50% Load

 
dBA
 
64/55
 
65/56
 
65/56
 Operation temperature  
°C
 
0 – 40
 

Ambient Temperature for

BATTERIES & RECTIFIERS (recommended)

 
°C
 
20 – 25
 Storage Temperature  
°C
 
-25 – +70
 

Battery Storage Time at Ambient

Temperature

   
Max. 6 months
 Max. altitude (above sea level)  
m
 
1000m (3300ft) without de-rating
 

De-rating factor for use at

altitudes above 1000m sea level according

( IEC 62040-3)

   

Meter above sea level (m / ft)

1500 / 4850

2000 / 6600

2500 / 8250

3000 / 9900

 

De-Rating Factor for Power

 0.95

 0.91

0.86

0.82

 Relative Air-humidity    
Max. 95% (non-condensing)
 Accessibility    

Totally front accessibility for service and maintenance

(no need for side, top or rear access)

 Positioning    
Min. 20 cm rear space (required for fan)
 Input and Output Power Cabling    
From the bottom on the front
 

Efficiency AC-AC up to (at cosphi 1.0)

(depending on Module power)

 
%
 
Load : 100% 75% 50% 25%
 
DPA 30-50: 95.2% 95.5% 95.7% 94.5%
 

Efficiency Non-linear Load

(EN 62040-1-1:2003)

   
Typically up to 1 % lower of above values
 Eco-Mode efficiency at 100% load  %  
98%

Standards


 Safety  

Product Standards

IEC/EN 62040-1

 

Standards

IEC/EN 60950-1

 

Electromagnetic

Compatibility

 

Product Standards

IEC/EN 62040-2

 

Standards

IEC/EN 61000-6-2 ; IEC/EN 61000-6-4
IEC/EN 61000-4-2 ; IEC/EN 61000-4-3
IEC/EN 61000-4-4 ; IEC/EN 61000-4-5
IEC/EN 61000-4-6

 EMC Classification  
DPA-30
 
DPA-40
 
DPA-50
 Emission Class  
C2
 
C2
 
C2
 Immunity Class  
C3
 
C3
 
C3
 Performance  
IEC/EN 62040-3
 Product certification  
CE
 Degree of protection  
IP 20

Communication


 Power Management Display (PMD)  1 LCD display for each module
 Serial ports RS232 on Sub-D9  

 2x system frame + 1x on each module (Smart Port)

 For monitoring and integration in network management

 USB  1x For monitoring and software management
 

Customer Interfaces : Inputs

DRY PORT X1

 

 1 Remote Shut down [EMERGENCY OFF (Normally closed)]

 1 GEN-ON (Normally open)

 2 Programmable Customer’s Inputs (Normally open)

 1 Temp. Sensor for Battery Control

 

Customer Interfaces : Outputs

DRY PORT X2 , X3, X4

 

10 voltage free contacts

For remote signalling and automatic computer shutdown

 Slot for SNMP  

SNMP card (optional)

For monitoring and integration in network management


Power Management Display (PMD)


The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides the necessary monitoring information about the UPS

MIMIC Diagram


The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the corresponding LEDindicators will change colour from green (normal) to red (warning). The LED’s LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s INVERTER and BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time the audible alarm will be activated.

Display


The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer from INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for adjustments and testing (for more details see the USER MANUAL of Conceptpower DPATM S2).

dpa-display

Power Management Display (PMD) of Conceptpower DPM TM S2

CUSTOMER INTERFACES (Terminals X1….X4)


CUSTOMER INPUTS DRY PORT s: Terminal block X1


Connection of Remote Shut down facilities, Generator Operation, Customers specials (see UM Section 9 / OPTIONS)

CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X2, X3, X4


Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems

All voltage free contacts are rated 60 VAC max. and 500 mA max.:

All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm2

phoenix-spring

Phoenix Spring Terminals (X1…X4) Connection

OPTIONS


  • SNMP card and WaveMon Management Software , Modbus Protocol
  • External Battery Cabinets
  • Parallel bus for additional frames
  • In/Output Transformator for special voltages
  • Temp. sensor for battery temp. control

SNMP card / WaveMon Management Software


The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-protocol. It is used to monitor any device in the network via simple control language. The UPS-Management Software WaveMon also provides its data in this SNMP format with its internal software agent. The operating system you are using must support the SNMP protocol. We offer our WaveMon software with SNMP functionality for Novell, OS/2, all Windows running on INTEL and ALPHA, DEC VMS, Apple.

Two types of SNMP interfaces with identical functionality are available: an external SNMP-Adapter (Box) and an internal SNMP-Card. Both can manage a parallel system (N modules) and return either global values - which are consistent for the whole parallel system - or specific values from the single modules.


 

S-type = For Separate. Battery

C-type = For Common. Battery

   

CBAT-DPA-120

S-type or C-type

 

CBAT-DPA-200

S-type or C-type

 BATTERY FRAMES  
battery-frames
battery-frames
 Configuration accommodates:  Max.  

120 Batt. block x 24Ah/28Ah

on 8 shelf

3x5=15 blocks/shelf

 

200 Batt. blocks x 24Ah/28Ah

on 7 shelf

6x5=30 blocks/shelf

 

Battery fuses / Max. Batt. Strings :

Terminals :

 S-type  

3 / 3

(Terminal 9 x 16/25mm2)

 

5 / 5

(Terminal 15 x 16/25mm2)

 

Battery fuses / Max. Batt. Strings

Terminals :

 C-type  

3 / 3

+ Com. Connection Bar

3 x (2xM8) +PE 2xM8

 

5 / 5

+ Com. Connection Bar

3 x (2xM10) +PE 2xM10

 Fuse Type (Very Fast acting)  
A
 
3x100 A
 
5x100 A
 Dimensions (WxHxD)  
mm
 
730x1975x800
 
1200x1975x800
 Weight with trays and w/o BATTERIES & RECTIFIERS  
kg
 
290
 
410
 

 Possible Battery configurations

 within the Battery Cabinets

   

Battery Configurations

30x28Ah

40x28Ah

50x28Ah

(2x30)x28Ah

(2x40)x28Ah

(2x50)x28Ah

(3x30)x28Ah

(3x40)x28Ah

 

Battery Configurations

(2x40)x28Ah

(3x40)x28Ah

(4x40)x28Ah

(5x40)x28Ah

(2x50)x28Ah

(3x50)x28Ah

(4x50)x28Ah

(5x30)x28Ah

(5x40)x28Ah

 

Go to the top

BATTERY AUTONOMIES


MX Modules: Examples of Internal Battery Autonomy

 Module Type  DPA 30  DPA 40  DPA 50
 Separate Battery configuration  
Battery Autonomy in (min.) per Module
 Frame Type  

Battery / Module

(up to 3 modules / within Triple-150 frame)

 
30kVA/24KW
 
40KVA/32KW
 
50KVA/40KW
 

CLASSIC DPA-50

or TRIPLE DPA-150

 (2x40)x9Ah  
8
 
6
 
 Common Battery configuration  
Battery Autonomy in (min.) for Tot. System Power
 With 1 Module  

Module Type

Total System Power

 

1 x DPA 30

30kVA/24KW

 

1 x DPA 40

40KVA/32KW

 

1 x DPA 50

50KVA/40KW

 CLASSIC DPA-50  (2x50)x9Ah  
11
 
8
 
 CLASSIC DPA-50  (3x40)x9Ah  
14
 
9
 
 CLASSIC DPA-50  (3x50)x9Ah  
18
 
13
 
9
 CLASSIC DPA-50  (4x50)x9Ah  
26
 
18
 
14
 CLASSIC DPA-50  (5x50)x9Ah  
34
 
24
 
18
 With 2 Modules  

Module Type 2

Total System Power

 

x DPA 30 2

60kVA/48KW

 

x DPA 40

80kVA/64KW

 

2 x DPA 50

100kVA/80KW

 TRIPLE DPA-150  2x(2x40)x9Ah  
8
   
 TRIPLE DPA-150  3x(2x40)x9Ah  
14
 
9
 
7
 With 3 Modules  

Module Type

Total System Power

 

3 x DPA 30

90kVA/72KW

 

3 x DPA 40

120kVA/96KW

 

3 x DPA 50

150kVA/120KW

 TRIPLE DPA-150  3x(2x40)x9Ah  
8
 
6
 

MX Modules: Examples of External Battery Autonomy


This configuration are mostly used in combination with the frame UPGRADE DPA-250

 Module Type  DPA 30  DPA 40  DPA 50
 Separate Battery configuration  
Battery Autonomy in (min.) per Module
 

Battery Cabinet

(for up to 5 modules linked)

 Battery / Module  
30kVA/24KW
 
40KVA/32KW
 
50KVA/40KW
 1x CBAT-DPA-200  40x28Ah  
13
 
9
 
7
 Common Battery configuration  
Battery Autonomy in (min.) for Tot. System Power (4+1)
 With 4 Modules  

Module Type

Total System Power

 

4 x DPA 30

120kVA/96KW

 

4 x DPA 40

160kVA/128KW

 

4 x DPA 50

200kVA/160KW

 1x CBAT-DPA-120  (3x40)x28Ah  
9
 
6
 
 1x CBAT-DPA-200  (3x50)x28Ah  
12
 
9
 
 1x CBAT-DPA-200  (4X50)x28Ah  
18
 
12
 
9
 2x CBAT-DPA-200  5x (2x40) x 28Ah  
43
 
30
 
22

INSTALLATION PLANNING

 


installation-planning

 UPS Frame type (50kVA up to 250 kVA)  CLASSIC DPA-50  TRIPLE DPA-150  UPGRADE DPA-250
 Dimensions (WxHxD) mm  730x1650x800  730x1975x780  730x1975x800
 Battery Cabinet Type  NA  CBAT DPA-120  CBAT DPA-200
 Dimensions (WxHxD) mm  NA  730x1975x800  1200x1975x800
 Accessibility  Totally front accessibility for service and maintenance (no need for side, top or rear access)
 Positioning Min.  20 cm rear space (required for fan)
 Input and Output Power Cabling  From the bottom on the front

HEAT DISSIPATION PER MODULE WITH NON-LINEAR LOAD


 Module size  
MX
 Module Type  
DPA 30 S2
 
DPA 40 S2
 
DPA 50 S2
 

 Heat Dissipation with 100%  Non-linear

 Load per Module (EN  62040-1-1:2003)

 
W
 
1532
 
2043
 
2553
 

 Heat Dissipation with 100%  Non-linear

 Load per Module (EN  62040-1-1:2003

 
BTU
 
5227
 
6969
 
8712
 

 Airflow (25° - 30°C) with Non-linear

 Load per Module (EN  62040-1-1:2003)

 
m3/h
 
380
 
380
 
380

WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES


The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such as a licensed service engineer from the manufacturer or from an agent authorised by the manufacturer. More details and procedure are mentioned in the user manual.

TERMINAL CONNECTIONS OVERVIEW


 

FRAME TYPE

Terminals (T) Connection Bar (B)

 

Separate. Battery

(+ / N / - ) +PE

 

Common Battery

(+ / N / - ) +PE

 

Input Bypass

3+N

 

Input Rectifier

3+N+PE

 

Output load

3+N+PE

 CLASSIC DPA-50  3+1 x 16/25mm2 (T)  3+1 x 16/25mm2 (T)  4 x 16/25mm2 (T)  5 x 16/25mm2 (T)  5 x 16/25mm2 (T)
 TRIPLE DPA-150  

9+1 x 16/25mm2 (T)

+PE 1xM10 (B)

 

3 x M10 (B)

+PE 1xM10 (B)

 

3 x M10(B)

+PE 1xM10 (B)

 

4 x M10 (B)

+PE 1xM10 (B)

 

4 x M10 (B)

+PE 1xM10 (B)

 UPGRADE DPA-250  

15 x 16/25mm2 (T)

+PE 1xM12 (B)

 

3 x M12 (B)

+PE 1xM12 (B)

 

3 x M12 (B)

+PE 1xM12 (B)

 

4 x M12 (B)

+PE 1xM12 (B)

 

4 x M12 (B)

+PE 1xM12 (B)

 


classic-dpa-50
triple-dpa-150
upgrade-dpa-250

SINGLE FEED INPUT


Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected

single-feed-input


 

Frame

type

 

Load

kVA

cosphi

0.8

 Input 3x400V  Output 3x400V cosphi 0.8  Battery
 

Fuse A

(Agl/CB)

 

Cable A (mm2)

(IEC 60950-1)

 

Max. Input

Current

with

battery c

harging

(A)

 

Cable D (mm2)

(IEC 60950-1)

 

I nom

(A)

 

Fuse E

+ / N / -

(Agl/CB)

 

Cable E (mm2)

for CBAT DPA 120 or 200

ONLY

+ / N / -

 Com. Battery Sep. Battery
 MX Frames (Frames shall be cabled to there full rating capability)
 CLASSIC DPA 50  50  3x100A  5x25  67  5x25  72 A  3x100A*1  3x25  3x25
 TRIPLE DPA-150  150  3x250A  5x120 or 5x(2x50)  202  5x120 or 5x(2x50)  218 A  3x300A*1  3x150  3x(3x25)
 UPGRADE DPA-250  250  3x400A  5x(2x95)  337  5x(2x95)  362 A  3x500A*1  3x(2x150)  5x (3x25)
 Other intermediate Ratings (we recommend to cable the frame mentioned above at full rating to able future upgrading)
   30  3x63A  5x10  40  5x10  43 A  3x80A  3x16  
 40  3x80A  5x25  54  5x25  58 A  3x100A*  3x25*
 45  3x100A  5x25  68  5x25  65 A  3x125A*  3x35*
 60  3x100A  5x25  81  5x25  87 A  3x125A*  3x35*
 80  3x125A  5x50  108  5x50  116 A  3x160A*  3x50*
 90  3x160A  5x50  121  5x50  130 A  3x200A*  3x70*
 100  3x160A  5x50  135  5x50  145 A  3x224A*  3x95*
 120  3x200A  5x70  161  5x70  174 A  3x250A*  3x120*
 160  3x250A  5x120 or 5x(2x50)  215  5x120 or 5x(2x50)  232 A  3x350A*  3x(2x70)*
 200  3x315A  5x185 or 5x(2x70)  267  5x185 or 5x(2x70)  290 A  3x450A*  3x(2x95)*

DUAL FEED INPUT


Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected

Dual Feed Input

 

Frame

Type

 

Load

kVA

cosphi

0.8

 Input 3x400V  Bypass 3x400V  Output 3x400V cosphi 0.8  Battery
 

Fuse B

(Agl/CB)

 

Cable B (mm2)

(IEC 60950-1)

 

Max. Input

Current

with

battery c

harging

(A)

 

Fuse C

(Agl/CB)

 

Cable
C
(mm2)
(IEC
60950-1)

 

Cable D (mm2)

(IEC 60950-1)

 

I nom

(A)

 

Fuse E

+ / N / -

(Agl/CB)

 

Cable E (mm2)

for CBAT DPA 120 or 200

ONLY

+ / N / -

 Com. Battery Sep. Battery
 MX Frames (Frames shall be cabled to there full rating capability)
 CLASSIC DPA 50  50  3x100A  5x25  67  3x100A  4x25  5x25  72 A  3x100A*1  3x25  3x25
 TRIPLE DPA-150  150  3x250A  5x120 or 5x(2x50)  202  3x250A  4x120 or
4x(2x50)
 5x120 or
5x(2x50)
 218 A  3x300A*1  3x150  3x
(3x25)
 UPGRADE DPA-250  250  3x400A  5x(2x95)  337  3x400A  4x(2x95)  5x(2x95)  362 A  3x500A*1  3x(2x150)  5x
(3x25)
 Other intermediate Ratings (we recommend to cable the frame mentioned above at full rating to able future upgrading)
   30  3x63A  5x10  40  (3x25)  4x10  5x10  43 A  3x80A  3x16  
 40  3x80A  5x25  54  3x80A  4x25  5x25  58 A  3x100A*  3x25*
 45  3x100A  5x25  68  3x100A  4x25  5x25  65 A  3x125A*  3x35*
 60  3x100A  5x25  81  3x100A  4x25  5x25  87 A  3x125A*  3x35*
 80  3x125A  5x50  108  3x125A  4x50  5x50  116 A  3x160A*  3x50*
 90  3x160A  5x50  121  3x160A  4x50  35x50  130 A  3x200A*  3x70*
 100  3x160A  5x50  135  3x160A  4x50  5x50  145 A  3x224A*  3x95*
 120  3x200A  5x70  161  3x200A  4x70  5x70  174 A  3x250A*  3x120*
 160  3x250A  5x120 or 5x(2x50)  215  3x250A  4x120 or
4x(2x50)
 5x120 or
5x(2x50)
 232 A  3x350A*  3x(2x70)*
 200  3x315A  5x185 or 5x(2x70)  267  3x315A  4x185 or
4x(2x70)
 5x185 or
5x(2x70)
 290 A  3x450A*  3x(2x95)*