STAND ALONE UPS SYSTEMS

MODULAR UPS SYSTEMS

BATTERIES & RECTIFIERS


SOLAR PRODUCTS


ConceptpowerTM Modular

 

60-80-100kVA
Uninterruptible Power Supply (UPS)
Modular, n+1 redundant, three-phase
On-line, Double-Conversion, VFI
Upgrade-Line 60-80-100kVA

TECHNICAL SPECIFICATIONS



60, 80 and 100 kVA (three phase input and output)

GENERAL DATA



Output Rated Power kVA
60
80
100
Output Power Factor  
0.8
Topology  
On-Line, Double Conversion, VFI
Technology  
Second Generation, Transformerless
Construction  
Modular, Parallelable
Parallel Configuration  
For redundancy and/or capacity:
- Standard up to 10 modules
- Without limitation on request
Double Conversion AC-AC efficiency with batt. fully charged  
100%/75%/50%25% Linear Load (cos!􀒏=0.8ind)
%
95/95/93.5/92
95/95/93.5/92
95/95/93.5/92
100%/75%/50%/25% Linear Load (Resistive cos!=1)
%
94/94/92.5/91
94/94/92.5/91
94/94/92.5/91
100%/75%/50%/25% Non-linear Load (EN 62040-1-
1:2003)
%
93/93/91/90
93/93/91/90
93/93/91/90
Eco-Mode efficiency (load on by-pass) at 100% load %
98
98
98
Heat Dissipation With 100% Load (cos􀒏!􀒏=0.8ind) W
2600
3400
4200
Heat Dissipation With 100% Load (Resistive cos􀒏!􀒏=1) W
3100
4100
5100
Heat Dissipation With 100% Non-linear Load (EN 62040-1-
1:2003)
W
3650
4850
6100
Airflow (25° - 30°C) with Non-linear Load (EN 62040-1-1:2003) m
3
/h
1500
1500
1500
Audible Noise of Module with 100% / 50% Load dBA
69/65
69/65
69/65
Ambient Temperature for UPS °C
0 – 40
Ambient Temperature for Batteries (recommended) °C
20 - 25
Storage Temperature °C
-25 - +70
Battery Storage Time at Ambient Temperature  
Max. 6 months
Cooling  
Fan-assisted
Relative Air-humidity  
Max. 95% (non-condensing)
Standards
- Safety
 
EN 62040-1-1:2003, EN 60950-1:2001/A11:2004
- Electromagnetic Compatibility  
EN 50091-2:1995, EN61000-3-2:2000, EN6100-3-3:1995/A1:2001,
EN61000-6-2:2001, EN61000-6-4:2001
- Performance  
EN62040-3:2001
Transportation Palette  
Provided with UPS
Accessibility  
Totally front accessibility for service and maintenance (no need for side, top
or rear access)
Positioning  
Min. 20cm rear space (required for fan)
Input and Output Power Cabling  
From front and bottom or top (on request)
Dry Port (Volt-free contacts)  
For remote signalling and automatic computer shutdown
Smart Port (RS 232)  
For monitoring and integration in network management
Input Terminals  
EMERGENCY OFF (Normally closed)
GEN-ON (Normally open)
BATTERY TEMP. SENSOR
UPS Module Weight
-Active Module
-Passive Module
kg
60kVA = 60kg, 80kVA = 65kg ; 100kVA = 65kg
60kVA = 65kg, 80kVA = 70kg ; 100kVA = 85kg
UPS Module Size (WxHxD)
-Active Module
-Passive Module
-Cabinet (Upgrade frame 300kVA)
mm
667 x 412 x 834
667 x 412 x 834
1400 x 1900 x 870

RECTIFIER DATA



Input Voltage V 3x380/220V+N, 3x400V/230V+N, 3x415/240V+N
Input Voltage Tolerance (ref to 3x400/230V) V (%) For Loads: <100%(-23%,+15%)
<80%(-30%,+15%)
<60%(-40%,+15%)
Input Frequency Hz 35 – 70
Input Power Factor   0.98
Input Current Form   Sinewave THDI = 7􀁹9% at 100% load
Inrush Current   Limited by soft start
Model kVA 60 80 100
Input Power with rated output power and charged battery kW 52 69 86
Max. Input Power with rated output power and discharged battery kW 56 75 93


Go to the top


BATTERY DATA



Maximum Battery Charger Current (standard) 16 A
Battery Charging Curve IU (DIN 41773)
Temperature Controlled Battery Charger Yes
Battery Charger Ripple Ripple-free battery charging
Battery Test Automatic and periodic (adjustable)
Battery Type Lead-acid, Maintenance-free and NiCd
Variable Number of 12V Battery Blocks For modules 60 and 80kVA use 40-50 blocks (only even numbers allowed)
For modules 100kVA use:
40 battery blocks for back-up times less then 10minutes
42 battery blocks for back-up times less then 15minutes
44 battery blocks for back-up times less then 20minutes
48 or 50 battery blocks for back-up times more then 20min.


INVERTER DATA



Output Rated Power
KVA
60
80
100
Output Rated Voltage
V
3x380/220V, 3x400/230V, 3x415/240V
Output Power Factor
0.8
Output Voltage Stability

- Static

%
< +/- 1

- Dynamic (with load Step 0-100%, 100-0%)

%
< +/- 4
Output Voltage Distortion

- With Linear Load

%
+ / - 2

- With Non-linear Load (EN62040-3:2001)

%
< +/- 3
Recovery Time After Load Jump (0-100%, 100-0%)
msec
20
Permissible Unbalanced Load
%
100% (all 3 phases regulated independently)
Output waveform
sinewave
Output Frequency
Hz
50 or 60
Output Frequency Tolerance

- Free-running, Quartz Oscillator

%
+ / - 0.1

- Synchronized with mains (adjustable)

%
+ / - 4
Overload Capability
%
125 for 10min. and 150 for 1min.
Crest - Factor
3 : 1


POWER MANAGEMENT DISPLAY (PMD)

The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides the necessary monitoring information about the UPS.

MIMIC DIAGRAM

The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the corresponding LED-indicators will change colour from green (normal) to red (warning). The LED’s LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s INVERTER and BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time the audible alarm will be activated.

PUSHBUTTONS

The pushbuttons serve to manage the UPS by performing commands. The 2xON/OFF pushbuttons serve to start-up or shutdown the UPS if pressed simultaneously. The pushbuttons UP and DOWN allow working through the PMD-menu. The RESET pushbutton serves to cancel the audible alarm in the event of a disturbance. If the alarm condition was only transient the LED-indicator ALARM would also extinguish otherwise it will remain on (red).

DISPLAY

The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer from INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for adjustments and testing (for more details see the USER MANUAL of ConceptpowerTM).
Concept Power

Power Management Display (PMD) of ConceptpowerTM



OPTIONALS

Optional Battery Charger
For longer autonomies
Remote Signalling Panel (RSP)
For UPS-Status indication
Parallel Configuration (standard)
A number of units may be paralleled
for redundancy or capacity upgrade
Wavemon Software
For automatic shut-down and monitoring
SNMP - Adapter
For network management and remote monitoring
Input or Output Isolation Transformer
For special voltages or for galvanic isolation
Customized UPS- and Battery Frames
On request (for OEM-Projects only)



MECHANICAL CHARACTERISTICS Upgrade Line



MODEL
KVA 3x60 3x80 3x100
Dimensions (WxHxD) mm
1400 x 1900 x 870
Protection Degree  
IP 20
Ventilation  
Fan assisted
Colour  
RAL 9002
Foot Print m
2
1.22
Maximum Output Power of one Upgrade Line UPS  
300 kVA


Dimensions of Concept Power (depth 870mm)
CUPS-300U




Dimensions of concept power
Power
(kVA)
Autonomy
(min.)
Frame
Type
Weight
(kg)
60
0
CUPS-300U
465
60 + 60
0
CUPS-300U
590
60 + 60 + 60
0
CUPS-300U
715
80
0
CUPS-300U
475
80 + 80
0
CUPS-300U
610
80 + 80 + 80
0
CUPS-300U
745
100
0
CUPS-300U
490
100 + 100
0
CUPS-300U
640
100 + 100 + 100
0
CUPS-300U
790


Block Diagram

Cable Sections and Fuse Ratings recommended by European standards.
Alternatively, local standards to be respected



STANDARD VERSION (SINGLE FEED INPUT)



Power (kVA)
Fuse B
(Agl/CB)
Cable A
(IEC 60950-1:2001)
Cable D
(IEC 60950-1:2001)
Fuse E
+/N/-
60
3x100
5x25
5x25
3x125A
60+60
3x200
5x70
5x70
3x250A*
60+60+60
3x315
5x185 or 5x(2x70)
5x185 or 5x(2x70)
3x450A*
80
3x125
5x35
5x35
3x160A
80+80
3x250
5x120 or 5x(2x50)
5x120 or 5x(2x50)
3x350A*
80+80+80
3x400
5x240 or 5x(2x95)
5x240 or 5x(2x95)
3x630A*
100
3x160
5x50
5x50
3x224A
100+100
3x315
5x185 or 5x(2x70)
5x185 or 5x(2x70)
3x450A*
100+100+100
3x450
5x300 or 5x(2x95)
5x300 or 5x(2x95)
3x630A*



VERSION ON REQUEST (DUAL FEED INPUT)



Power (kVA)
Fuse B
(Agl/CB)
Cable B
(IEC 60950-1:2001)
Fuse C
(Agl/CB)
Cable C
(IEC 60950-1:2001)
Cable D
(IEC 60950-1:2001)
Fuse E
+/N/-
Cable E
+/N/-
60
3x100
5x25
3x100
4x25
5x25
3x125A
3x35
60+60
3x200
5x70
3x200
5x70
5x70
3x250A*
3x120*
60+60+60
3x315
5x185 or 5x(2x70)
3x315
5x185 or 5x(2x70)
5x185
3x450A*
3x(2x95) *
80
3x125
5x35
3x125
4x35
5x35
3x160A
3x50
80+80
3x250
5x120 or 5x(2x50)
3x250
5x120 or 5x(2x50)
5x120
3x350A*
3x(2x70) *
80+80+80
3x400
5x240 or 5x(2x95)
3x400
5x240 or 5x(2x95)
5x240
3x630A*
3x(2x150) *
100
3x160
5x50
\3x160
5x50
5x50
3x224A
3x95
100+100
3x315
5x185 or 5x(2x70)
3x315
5x185 or 5x(2x70)
5x185
3x450A*
3x(2x95) *
100+100+100
3x450
5x300 or 5x(2x95)
3x450
5x300 or 5x(2x95)
3x(2x150)
3x630A*
3x(2x150) *