STAND ALONE UPS SYSTEMS

MODULAR UPS SYSTEMS

BATTERIES & RECTIFIERS


SOLAR PRODUCTS


Technical Specifications Powervario 6kva

 

PowerVario highlights at a glance

  • Tower or Rack Version
  • Hot-Swap able battery exchange
  • N+1 Redundancy

Specifications

 


VA Rating

Model PVO11/4.5k PVO11/6k
Apparent Output Power 4500 VA 6000 VA
Active Output Power 3250Watts 4200Watts
Power Factor 0.7
Topology Double conversion On-Line
Type Rack/Tower
Agency Approvals 230V Models: CE

 

Input

Model PVO11/4.5k PVO11/6k
  230V 160 - 288Vac
Voltage
Range
 
Low Line
Transfer
230V 168Vac
Low Line
Comeback
230V 170Vac
High Line
Transfer
230V 288Vac
High Line
Comeback
230V 278Vac
Frequency 50/60 Hz auto-select, ± 5Hz
Phase Single phase with ground
PF >0.99 at full rated linear load
Typical Transfer Time 0 ms.
AC Leakage current 230V ≤ 3.5mA
Surge Protection 230V 300 joules

 

Output

Model PVO11/4.5k PVO11/6k
Output
(INV.
mode)
Voltage 230V 230V,adjustable to 200/208/220/230/240 via display
Voltage Regulation ≤± 1% until low battery warning
Frequency(Synchronized Range) 3Hz or 1Hz (setting by software)
Frequency(Battery Mode) ±0.1% (0.05~0.06Hz) unless synchronized to line
Current Crest Factor 3:1
Harmonic Distortion ≤3% THD(Linear Load)
≤7%THD(Non-Linear Load)
Transient Response(ms) 60ms/5%
Waveform Pure Sine wave
Efficiency To AC Mode (Full load) 90% 91%
To Battery Mode (Full load) 89% 89%

 

Battery System

Model PVO11/4.5k PVO11/6k
Type 12V/7.2Ah 12V/7.2Ah
Numbers of BATTERIES & RECTIFIERS 20 20
Backup Time(Full Load) >10min. >7min.
Recharging Time 4 Hours to 90%
Charging Current (Max.) 5 A
Charging Voltage 240.0Vdc±0.5V
Hot Swappable Battery Yes
Internal battery Yes
DC leakage current ≤ 30uA (±10uA) with no AC applied and the unit in the off position
Battery type Sealed, non-spillage, maintenance-free, lead acid

 

Transfer Time

Model PVO11/4.5k PVO11/6k
AC to DC Zero
Inverter to Bypass Zero
DC Start Yes
Self Diagnostics Upon Power-on and Software Control

 

back to top

 

Front Panel

Model PVO11/4.5k PVO11/6k
LED Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass
Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/ Fault/
Overload/Programmable Outlet1//Programmable Outlet2
Key ON Button/ OFF Button/ (Test/Alarm Reset Button) Function
Button

 

Protection

Model PVO11/4.5k PVO11/6k
Overload (AC Mode) 105 – 150 % for 160 seconds before transfer to bypass
(Bypass Mode) 105 – 200 % for 500 seconds shuts down
Buzzer continuously alarms.
Short Circuit Bypass mode : Input Fuse/Input Breaker
Normal Mode: Electronic Circuit – switch off
Battery Mode: Electronic Circuit– switch off
Battery ABDM
EPO UPS shuts down immediately
Over
Temperature
Transfer to Bypass
Mode
Transfer to Bypass Mode
UPS shuts down
immediately
UPS shuts down immediately

 

Audible Alarm

Model PVO11/4.5k PVO11/6k
Battery Mode Sounding once every 1.5 seconds
Low Battery Sounding once every 0.2 seconds
Overload Sounding once every 3 second
Fault Continuously Sounding(or Sounding once every 3 second)

 

Physical

Model PVO11/4.5k PVO11/6k
Dimensions(HxWxD in mm) 88.8(2U)x440(17”)x650 +
Battery Cabinet 132.(3U)x440(17”)x650
Weights 95kg
Input Connection 230V Fix or Connector
Fix or Connector
16A, IEC 320-C20
Output Connection 230V Fix or Connector

 

Environmental

Model PVO11/4.5k PVO11/6k
Operation Temperature 0-40 degrees
Noise Level 50dBA
Relative Humidity 0 to 90% (Without condensation)

 

Interface

Model PVO11/4.5k PVO11/6k
Interface Type 1 *USB port+ 1*RS-232 port + SNMP Slot
SNMP(option) Power management from SNMP manager and Web browser
Compatible platforms Windows 95/98/NT/2000/XP Novell NetWare, Linux, etc.

 

Standards and Certification

Model PVO11/4.5k PVO11/6k
Safety IEC/EN 62040-1-1,IEC 60950-1
Performance IEC/EN 62040-3
EMC EN50091-2/IEC 62040-2 class A
IEC 61000-4-2/-3/-4/-6-8/-11,IEC 61000-3-2/-3
Markings CE

 

back to top